A Zigzag Connected Auto-Transformer Based 24-Pulse AC-DC Converter

  • Published : 2008.06.30

Abstract

In this paper, a 24-pulse AC-DC converter is designed, modeled, simulated, and developed to feed non-isolated varying loads. The proposed AC-DC converter configuration consists of an auto-transformer based on zigzag connection to overcome current harmonic problems in AC mains. It improves power quality at AC mains and it meets IEEE-519 standard requirements at varying loads. A set of power quality indices on input AC mains and on DC buses for a load fed from 6-pulse and 12-pulse AC-DC converters is also given to compare their performance. It is observed that input current total harmonic distortion(THD) of less than 8% is possible with the proposed topology of AC-DC converter at varying loads.

Keywords

References

  1. IEEE Recommended Practice for Establishing Transformer Capability When Supplying Nonsinusoidal Currents, ANSI/IEEE C57.110-1986, New York, 1988
  2. IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, IEEE Standard 519-1992, IEEE Inc., New York, 1993
  3. B. K. Bose, Modern Power Electronics and AC Drive, Pearson Education, New Delhi, 2001
  4. G. Seguier, Power Electronic Converters: AC-DC Conversion, McGraw Hill Book Company, New York, 1987
  5. V. A. Boshnyaga, L. P. Kalinin and V. M. Postolaty, "Pahse-shifter," U.S. Patent 4,013,942, Mar. 22, 1977
  6. D. A. Paice, "Power Electronic Converter Harmonics: Multipulse Methods for Clean Power," IEEE Press, New York, 1996
  7. D. A. Paice, "Wye connected 3-phase to 9-phase autotransformer with reduced winding currents," U.S. Patent No. 6,191,968 B1, Feb. 20, 2001
  8. D. W. Owens, "Autotransformer for use with multiple phase rectifiers," U.S. Patent 7049921, May 23, 2006
  9. C. L. Chen and G. K. Horng, "A new passive 28-step current shaper for three-phase rectification," IEEE Trans. on Industrial Electronics, vol. 47, no. 6, pp. 1212-1219, Dec. 2000 https://doi.org/10.1109/41.887948
  10. B. Singh, G. Bhuvaneshwari, and V. Garg, "24-pulse AC-DC converter for power quality improvements in vector controlled induction motor drives," Electric Power Components and System, vol. 34, 2006, pp. 1077-1098 https://doi.org/10.1080/15325000600630335