The Condensation Heat Transfer of R-22 and R-410A in an Inner Diameter Tube of 1.77 mm

내경 1.77 mm관내 R-22와 R-410A의 응축열전달

  • Son, Chang-Hyo (School of Mechanical Engineering, Pukyong National University) ;
  • Roh, Geon-Sang (Department of Refrigeration and Air-conditioning Engineering, Tong Myong University)
  • 손창효 (부경대학교 기계공학부) ;
  • 노건상 (동명대학교 냉동공조공학과)
  • Published : 2008.03.30

Abstract

The condensation heat transfer coefficients of R-22 and R-410A in a small diameter tube were investigated. The main components of the refrigerant loop consist of a receiver, a variable-speed pump, a mass flowmeter, an evaporator (preheater), and a condenser (test section). The test section consists of smooth, horizontal copper tube of 3.38 mm outer diameter and 1.77 mm inner diameter. The refrigerant mass fluxes varied from 450 to $1050\;kg/(m^2s)$ and the average inlet and outlet qualities were 0.05 and 0.95. The main results were summarized as follows : the condensation heat transfer coefficient also increases with increasing mass flux and quality. The condensation heat transfer coefficient of R-410A was slightly higher than that of R-22. Most of correlations proposed in the large diameter tube showed significant deviations with experimental data except for the ranges of low quality and low mass flux.

본 연구는 세관내 R-22와 R-410A의 응축 열전달 계수를 실험적으로 조사하였다. 냉매 순환루프의 주요 구성품은 수액기, 변속 액펌프, 질량유량계, 증발기(예열기), 응축기(시험부)로 구성된다. 시험부는 평활, 수평 동관으로 내관의 내경과 외경이 각각 1.77 mm와 3.38 mm이다. 냉매 질량유속은 $450{\sim}1050\;kg/(m^2s)$이고, 입출구 평균건도는 $0.05{\sim}0.095$이다. 주요 실험결과를 요약하면, 응축 열전달 계수는 질량유속과 건도이 증가할수록 증가하였고, R-410A의 응축 열전달 계수가 R-22에 비해 약간 높았다. 종래의 상관식과 비교한 결과, 저건도와 저질량유속을 제외하고는 실험값과 종래의 상관식으로 예측한 값의 차이가 큰 것으로 나타났다.