DOI QR코드

DOI QR Code

A Refurbishment life Diagnosis for Overhead Transmission Conductors using Dip Measurement

이도 측정에 의한 가공송전선 도체의 교체수명 진단

  • 김성덕 (한밭대학교 전기.전자.제어공학부)
  • Published : 2008.04.30

Abstract

Conductors in overhead transmission lines are exposed under various environmental conditions for a long period of time, so that they may be slowly degraded due to air pollutant or thermal history. Aged conductors may reduce power system reliability and public safety. Therefore, diagnosis of aged conductors in service becomes more important concerns with respect to keeping power delivery stable with a proper capability, replacing aged conductors, or constructing a new line. In this paper, we posed a new method to diagnose the refurbishment life and estimate the remaining life of aged conductors by measuring dips. As analyzing some relations of conductor temperature, conductor current, and tension load, it could be verified that dip exactly shows mechanical tension loss for aged conductor. Based on several simulation results, it was shown that the proposed method may be effectively used to diagnose the refurbishment life or remaining one of overhead conductors.

가공송전선 도체는 장기간 동안 다양한 환경조건에 노출되어 있으므로 공기오염원이나 열적 이력에 의하여 서서히 열화된다. 노화도체는 전력시스템의 신뢰성과 공중 안전을 감소시키다. 따라서 운용 중인 노화도체의 진단은 적정한 용량으로 전력을 안전하게 공급하거나 노화도체의 교체 또는 새로운 선로의 건설이라는 관점에서 매우 중요한 관심사가 되었다. 본 논문에서는 이도를 측정하여 노화도체의 교체수명을 진단하고 잔존수명을 추정하는 새로운 방법을 제안한다. 도체온도, 도체전류 및 장력 사이의 관계를 해석함으로써 이도가 노화도체의 기계적 인장손실을 정확하게 나타낼 수 있다는 것을 확인하였다. 몇 가지 수치해석결과를 토대로 제안된 방법이 가공도체의 교체수명이나 잔존수명을 진단하는데 효과적으로 사용될 수 있음을 보였다.

Keywords

References

  1. M.F. Ishac, I.F. Boulos, A.P. Goel and D.J. Horrocks, "Life extension of an existing transmission line", The Seventh international Conference on Transmission and Distribution Construction and Live Line Maintenance, pp. 17-23, Ohio, 1995
  2. D.L. Rudolph, "A systematic approach to the replacement of an aging distribution system", 1997 IEEE Rural Electric Power Conference, A4.1-8, Minneapolis, 1997
  3. R.L. Jackson, R.R. Gibbon, J.M. Ferguson and K.G. Lewis, "The condition of the supergrid and a strategy for refurbishment", International Conference on Revitalizing Transmission and Distribution Systems, pp. 44-48, 1987
  4. Draft standard for calculating the current-temperature relationship for bare overhead conductors, IEEE Standard P738, 1999
  5. 가공송전선의 전류용량, 일본 전기학회 기술보고 제660호, 1997
  6. 가공송전선용 전선 선정기준 - 1210, 한국전력공사, 2003
  7. 가공선 이도 설계기준 - 1211, 한국전력공사, 2003
  8. J. Sutton and K.G. Lewis, "The detection of internal corrosion in steel reinforced aluminum overhead power line conductors", U.K. Corrosion, pp.343-359, 1986
  9. D.G. Harvard, et. al, "Aged ACSR conductors. I. Testing procedures for conductors and line items", IEEE Transactions on Power Delivery, Vol. 7, No. 2, pp. 581-587, 1992 https://doi.org/10.1109/61.127052
  10. D.G. Harvard, et. al, "Aged ACSR conductors. II. Prediction of remaining life", IEEE Transactions on Power Delivery, Vol. 7, No. 2, pp. 588-595, 1992 https://doi.org/10.1109/61.127053
  11. J.M. Ferguson, and R.R. Gibbon, "Overhead transmission lines-refurbishment and developments", Power Engineering Journal, Vol. 8, No. 3, pp. 109-118, 1994 https://doi.org/10.1049/pe:19940303
  12. 송전운용업무기준, 한국전력공사 송변전처, 1999