A Study on Electric Field Distribution with Bushing Geometry

부싱 형상에 따른 전계 분포에 관한 연구

  • 조국희 (한국전기연구원 산업전기연구단)
  • Published : 2008.05.31

Abstract

This paper described results for desiging the best effective bushing geometry by comparing the distribution of the electric field according to bushing geometry. Twelve cases of the geometrical change are tried to analysis. Improvement of the insulation strength related with the vector and the electric field distribution are reached to about 0.7[%] and $21{\sim}26[%]$ by changing the electrode length, respectively. Moreover, in cases of the change of insulator thickness at high-voltage parts, the insulation strength relevant to the same parameters as mentioned above are 2[%] and $23{\sim}43[%]$, respectively Consequently, the quenching voltage for interrupting the partial discharge might be improved due to increasing the insulation strength by the geometrical change.

부싱의 형상에 따라 전계 분포를 비교하여 가장 효율적인 형상을 설계하고자 하였다. 본 연구에서 형상 변화는 12 조건이며 전극 길이의 변화로 벡터 분포도는 0.7[%], 전계 분포도는 약 $21{\sim}26[%]$의 절연 성능을 향상시킬 수 있었다. 그리고 고압부 절연물 두께의 변화는 벡터 분포도는 2[%], 전계 분포도는 약 $23{\sim}43[%]$의 절연 성능을 향상시킬 수 있었다. 따라서 조건변화에 따라 절연성능이 향상되는 것을 알 수 있으므로 부분방전 개시전압 소멸전압을 향상시킬 수 있을 것으로 사료된다.