$1{\times}3$ 행렬구조를 갖는 매트릭스형 초전도 한류기의 자장유무에 따른 퀜치특성 분석

Analysis on the Quench Characteristics According to Magnetic Field of the Matrix-Type SFCL with $1{\times}3$ Matrix Structure

  • 발행 : 2008.09.01

초록

We investigated the quench characteristics accordance with increase of turns and applied voltage of matrix-type superconducting fault current limiter (SFCL) with $1{\times}3$ matrixes. The matrix-type SFCL consists of the trigger part to apply magnetic field and the current-limiting part to limit fault current. The fault current limiting characteristics according to the increase of magnetic field and applied voltage were nearly same. This is because the application of magnetic field has not an affect on total impedance of SFCL. When number of turns of reactor increased, the voltage difference between two superconducting units in the current-limiting part according was decreased. The resistance difference generated in two superconducting units also was decreased. Therefore, we confirmed that the differences of critical behaviors between superconducting units by application of magnetic field were decreased. By this results, we could be decided the optimum number of turns of reactor to apply magnetic field.

키워드

참고문헌

  1. H.-S. Choi, Y.-S. Cho, S.-H. Lim, "Operational characteristics of hybrid-type SFCL by the number of secondary windings with YBCO films," IEEE Trans. Appl. Supercond., vol. 16, No. 2, pp. 719-722, June 2006 https://doi.org/10.1109/TASC.2006.871270
  2. S. Kozak, T. Janowski, "Physical and numerical models of superconducting fault current limiters," IEEE Trans. Appl. Supercond., vol. 13, No. 2, pp. 2068-2071, June 2003 https://doi.org/10.1109/TASC.2003.812989
  3. C.A. Baldan, C.Y. Shigue, D.S.S. Figueira, E.R. Filho, R.C. Freitas, "Test results of a superconducting FCL using bifilar coil of BSCCO-2212," IEEE Trans. Appl. Supercond., vol. 16, No. 2, pp. 695-698, June 2006 https://doi.org/10.1109/TASC.2006.871264
  4. H.-S. Choi, Y.-S. Cho, "Critical Current Equalization via Neutral Lines in a Transformer-Type SFCL," IEEE Trans. Appl. Supercond., vol. 18, No. 2, pp. 733-736, June 2008 https://doi.org/10.1109/TASC.2008.920635
  5. H.-S. Choi, S.-H. Lim, "Operating Performance of the Flux-Lock and the Transformer Type Superconducting Fault Current Limiter Using the YBCO Thin Films," IEEE Trans. Appl. Supercond., vol. 17, No. 2, pp. 1823-1826, June 2007 https://doi.org/10.1109/TASC.2007.898482
  6. O.-B. Hyun, S.-D. Cha, H.-R. Kim, H.-S. Choi, S.-D. Hwang, "Shunt-assisted simultaneous quenches in series-connected resistive SFCL components," IEEE Trans. Appl. Supercond., vol. 13, No. 2, pp. 2060-2063, June 2003 https://doi.org/10.1109/TASC.2003.812986
  7. D.-C. Chung, H.-S. Choi, N.-Y. Lee, G.-Y. Nam, Y.-S. Cho, T.-H. Sung, Y.-H. Han, B.-S. Kim, S.-H. Lim, "Optimum design of matrix fault current limiters using the series resistance connected with shunt coil," Physica C, vol. 463, pp. 1193-1197, Oct. 2007 https://doi.org/10.1016/j.physc.2007.03.457
  8. 산업자원부, "10kVA급 매트릭스형 초전도 한류기 개발 (연구보고서)", 2007