Experimental Study on Cooling Performance of Multi-Heat Pump by Indoor-Unit Combination

실내기 조합에 따른 3실형 열펌프의 냉방성능 실험연구

  • 권영철 (선문대학교 기계공학부) ;
  • 전종균 (선문대학교 기계공학부) ;
  • 박윤창 (선문대학교 정보통신공학부) ;
  • 고국원 (선문대학교 정보통신공학부) ;
  • 서동남 (선문대학교 기계공학부 대학원)
  • Published : 2008.12.31

Abstract

In order to investigate the cooling capacity of multi-heat pump applying an inverter compressor, the experiment on the cooling performance characteristics of heat pump with 3 indoor units was performed under the cooling standard and cooling low-temperature conditions. The system data were measured by the psychrometric calorimeter. The operation characteristics and the behavior of the cooling cycle of the heat pump with 3 indoor units were understood from the cooling capacity, COP, and P-h diagram by indoor-unit combination. The operating load and performance of the multi-heat pump depends on the indoor-unit combination. The cooling capacity and COP of the low temperature condition were larger than those of the standard one. Also the cycle was analyzed by using P-h diagram.

본 연구에서는 인버터 압축기를 적용한 3실형 멀티-열펌프 시스템의 냉방운전 시 시스템의 성능특성을 조사하였다. 시스템의 운전특성은 항온항습 기능을 가진 공기엔탈피방식의 칼로리미터를 이용하여 측정되었으며, 냉방표준 및 냉방저온 온도조건에서 실내기 조합에 따른 실험이 수행되었다. 3실형 열펌프의 실내기 조합운전에 따른 냉방 표준운전 및 냉방저온운전 시의 냉방능력, COP, P-h선도로부터, 3실형 열펌프의 운전특성과 냉방사이클의 거동을 이해하였다. 열펌프의 운전부하와 성능은 실내기 조합에 의존하므로 시스템의 능력과 사이클의 거동은 다르게 관찰되었다. 과냉도 증가와 압축일의 감소로 표준조건보다 저온조건에서 냉방능력과 COP가 더 높았다. 또한 P-h 선도를 이용하여 사이클의 운전특성도 분석하였다.

Keywords

References

  1. V. Bahel and S. M. Zubair (1989), "An assessment of inverter driven variable speed air conditioners: sample performance comparison with a conventional systems," ASHRAE Trans., Vol. 95, pp. 455-464.
  2. C. K. Rice and S. K. Fisher (1985), "Comparative analysis of single and continuously variable-capacity heat pump concepts", Proc. of the DOE/ORNL Heat Pump Conference, pp. 57-65.
  3. D. Y. Han, H. J. Kwon and S. C. Ha (1999), "Design and performance prediction of the multi-type heat pump system," Proceeding of the SAREK, pp. 515-520.
  4. H. H. Cho, Y. C. Kim and H. H. Park (1999), "Performance characteristics of an inverter-driven scroll compressor," Proceeding of the air-conditioning and Refrigeration Engineering, pp.1139-1143.
  5. G. H. Jung, H. D. Choi, M. H. Kim and S. K. Oh (2002), "An optimal control using a compressor discharge temperature on multi-type inverter heat pump," Proceeding of the SAREK, pp. 1241-1246.
  6. 한국표준협회 (1999), KS C 9306 : KS 에어컨디셔너.
  7. ASHRAE (1986), "Method of Testing for Rating Room Air Conditioner and Packaged Terminal Air Conditioner Heating Capacity," ANSI/ASHRAE Standard 58-1986.

Cited by

  1. Experimental Study on Heating Performance Characteristics of Air Source Heat Pump with Air to Water Type vol.23, pp.6, 2011, https://doi.org/10.6110/KJACR.2011.23.6.400