A Experimental Study on the Structural Performance of Column Spliceswith Metal Touch Subjected to Axial Force and Bending Moment

압축력과 휨모멘트를 받는 메탈 터치된 기둥 이음부의 구조성능에 대한 실험적 연구

  • Received : 2007.12.11
  • Accepted : 2008.09.02
  • Published : 2008.10.10

Abstract

The structural framework design uses high-strength bolts and welding in column splices. However, for the column under high compression, the number of the required high-strength bolts can be excessive and the increase of welding results in difficulty of quality inspection, the transformation of the structural steels, and the increase of erection time. According to the AISC criteria, when columns have bearing plates, or they are finished to bear at splices, there shall be sufficient connections to hold all parts securely in place. The Korean standard sets the maximum 25% of the load as criteria. Using direct contact makes it possible to transfer all compressive force through it. The objective of this study is to examine the generally applied stress path mechanism of welded or bolted columns and to verify the bending moment and compression transfer mechanism of the column splice according to metal touch precision. For this study,22 specimens of various geometric shapes were constructed according to the change in the variables for each column splice type, which includes the splice method, gap width, gap axis, presence or absence of splice material, and connector type. The results show that the application of each splice can be improved through the examination of the stress path mechanism upon metal contact. Moreover, the revision of the relative local code on direct contact needs to be reviewed properly for the economics and efficiency of the splices.

철골구조물의 기둥이음 형식은 볼트연결이나 용접을 이용한다. 이러한 연결방법에서 부재의 축응력은 덧판의 볼트체결이나, 용접부위 를 통하여 그 응력이 전달되는 것으로 간주하여 설계, 시공되고 있다. 우리나라의 강구조 한계상태 설계기준에 따르면, 기둥 이음부의 고력볼트 및 용접이음은 이음부의 응력을 충분히 전달하여야 하고 이들 항복내력은 피접합재 항복내력의 1/2이상이 되도록 하여야 한다. 다만, 이음부에서 단면 에 인장응력이 없는 경우, 이음면이 절삭 마감으로 밀착되면 소요압축력 및 소요휨모멘트 각각의 1/4은 접촉면에 의해 직접 전달시킬 수 있다고 되 어있다. 반면에, 미국 철강협회설계기준(AISC Specifications and Codes)에서는 기둥이음에서 지압력에 따라 응력이 전달되도록 접촉면이 마무리 되어 있는 경우, 그 위치를 확보하는데 충분하도록 이음되어야 한다고만 되어있어, 설계자의 판단에 따라 압축력은 이음면의 직접접촉(Metal Touch)으로 상부에서 하부로 모두 전달할 수 있도록 되어있고, 또한 압축력과 휨모멘트를 받는 기둥에서는 직접접촉을 통해 최소 25%에서 최대 50%까지의 하중전달이 가능하다. 따라서 기둥이음에서 압축력에 대한 직접접촉의 활용도의 차이가 크고 또한 압축력과 모멘트가 작용할 때의 직접 접촉에 대한 활용도도 그 차이가 최대 25%이므로, 직접 접촉된 이음부의 응력전달 거동에 대한 연구가 필요하다. 본 연구는 축력과 휨모멘트가 작 용하는 기둥에 대해서 이루어지며 실험체의 수는 총 22개이다. 국내의 메탈터치의 평활도인 관리 허용치 1.5D/1000와 한계허용치 2.5D/1000및 AISC에서 제시하는 압축력을 받는 기둥에서의 보강 없는 틈의 한계인 1.6mm에 대해, 본 실험결과와 기존의 허용치를 비교하였다. 그 결과, 상하 부재 간의 직접 접촉을 통하여, 즉 메탈터치를 이용하여 응력을 전달시키면 부재 이음에서 경제성과 효율성이 개선될 수 있다고 판단된다.

Keywords

References

  1. Popov, E.P. and Stephen, R.M.(1977) Capacity of Columns with Splice Imperfections, Engineering Journal of AISC, First Quarter.
  2. Gaylord, Edwin H. and Jr. Gaylord, Charles N.(1992) Design of steel structures 3rded. McGraw- Hill,Inc.
  3. Hong, Kappyo and Kim, Seokkoo(2004) A Study on the Behavior of Metal Touch Connection subject to Connection Types, Magazine of the Korean Society of Steel Construction, Vol.16 No.5
  4. Hong, Kappyo and Kim, Seokkoo(2004) A Study on the Behavior of stress path subject to the gap size of metal touch connection, Magazine of the Korean Society of Steel Construction, Vol.16 No.5
  5. Salmon, Charles G. and Johnson, John E.(1996) STEEL STRUCTURES Design and behavior 4thed., Harper Collins.
  6. Kim, Seokkoo(2004) A Study on the Stress Path and Code Improvement in Column Splice with Metal Touch, Ph.D Thesis, Yonsei University.
  7. Goel, Subhash C., Stojadinoviec Bozidar and Lee, Kyoung-Hyeog (1997) Truss Analogy for Steel Moment Connection, Engineering Journal of AISC, Second Quarter.
  8. Bruneau, Michel and Mahin, Stephen A.(1991) Full-Scale Tests of Butt-Welded Splices in Heavy-Rolled Steel Sections Subjected to Primary Tensile Stresses, Engineering Journal of AISC, First Quarter.
  9. Stentina, Henry J.(Oct 1963) Are Tier Building Column Splices Designed, AISC Engineering Journal, pp.144-145.
  10. Fisher, John W., Galambos, Theodore V., Kulak, Geoffrey L. and Ravindra, Mayasandra K.(Sep. 1978) Load and Resistance Factor Design Criteria for Connectors, Journal of the structural division, Vol. 104, pp.1427-1441 No.ST9.
  11. AICS(1999) LRFD Specification of structural steel building in Manual of steel construction, American Institute of Steel Construction, 3rded.
  12. Hong, Kappyo Tang, J.G. and Lee, S.K.(May 2001) Parametric Study of Double Angle Framing Connections Subjected to Shear and Tension, Journal of Construction Steel Research 57, pp.997-1013. https://doi.org/10.1016/S0143-974X(01)00019-0
  13. Hong, Kappyo Yang, J.G. and Lee, S.K.(2001) Moment -Rotation Behavior of Double Angle Connections Subjected to Shear Load, Engineering Structures, Vol 24/1 pp.125-132.
  14. Song, Hyun-su(2001) The Design of Steel Structure in Limit State, Taelim.
  15. AIK(1997) The Design Criteria of Steel Structure in Limit State, Architectural Institute of Korea.