A Performance Evaluation of a 400RT Vertical type Geothermal System installed in a R&D and Office Building in Spring

연구.사무공간의 냉난방용으로 설치된 400RT급 수직형 지열시스템의 봄철 성능평가

  • Shin, Dong-Keol (Graduate School of Korea Maritime University) ;
  • Kim, Joong-Hun (Institute of Construction Technology, Samsung Corporation) ;
  • Shin, Seung-Ho (Institute of Construction Technology, Samsung Corporation) ;
  • Hwang, Kwang-Il (Div. of Mechanical and Information Engineering, Korea Maritime University)
  • 신동걸 (한국해양대학교 냉동공조공학과 대학원) ;
  • 김중헌 (삼성건설 기술연구소) ;
  • 신승호 (삼성건설 기술연구소) ;
  • 황광일 (한국해양대학교 기계정보공학부)
  • Published : 2008.12.01

Abstract

400RT geothermal system which is consist with vertical-typed 112 geothermal heat exchangers is measured and evaluated in spring, 21st${\sim}$24th May 2008. As the results, the average temperature difference between inlet and outlet of geothermal pipes is $1{\sim}2^{\circ}C$ and that of cool water supply is $2{\sim}6^{\circ}C$, when being normally operated. Despite temperature fluctuations by cooling loads, the average temperature difference between main pipes of inlet and outlet of geothermal heat exchangers is measured as $3^{\circ}C$. The geothermal system COPs are calcluated as 2.92${\sim}$3.92 in every 12 hours.