DOI QR코드

DOI QR Code

Analysis of Magnetic Field Application Effect on Fault Current Limiting Characteristics of a Flux-lock Type SFCL

  • Published : 2008.12.31

Abstract

The magnetic field application effect on resistance of a high-$T_c$ superconducting (HTSC) element comprising a flux-lock type superconducting fault current limiter (SFCL) was investigated. The YBCO thin film, which was etched into a meander line using a lithography, was used as a current limiting element of the flux-lock type SFCL. To increase the magnetic field applied into HTSC element, the capacitor was connected in series with a solenoid-type magnetic field coil installed in the third winding of the flux-lock type SFCL. There was no magnetic field application effect on the resistance of HTSC element despite the application of larger magnetic field into the HTSC element when a fault happened. The resistance of HTSC element, on the contrary, started to decrease at the point of four periods from a fault instant although the amplitude of the applied magnetic field increased.

Keywords

References

  1. E. Floch, D. Buzon, D. Isfort, L. Porcar, X. Chaud, P. Tixador, D. Bourgault, and R. Tournier, "Current limitation based on bulk YBaCuO meanders", Cryogenics, Vol. 41, p. 531, 2001 https://doi.org/10.1016/S0011-2275(01)00099-6
  2. B. Gromoll, G. Ries, W. Schmidt, H.-P. Kramer, P. Kummeth, and H.-W. Neumuller, "Resistive current limiters with YBCO films", IEEE Trans.Appl. Superconduct., Vol. 7, No. 2, p. 828, 1997 https://doi.org/10.1109/77.614631
  3. K. Shimohata, S. Yokoyama, T. Inaguchi, S. Nakamura, and Y. Ozawa, "Design of a large current-type fault current limiter with YBCO films", Physica C, Vol. 372-376, p. 1643, 2002 https://doi.org/10.1016/S0921-4534(02)01088-2
  4. Y. Kudo, H. Kubota, H. Yoshino, and Y. Wachi, "Improvement of maximum working voltage of resistive fault current limiter using YBCO thin film and metal thin film", Physica C, Vol. 372-376, p. 1164, 2002
  5. D. Ito, C. Yang, O. Miura, M. Morita, and T. Tokunage, "kA class resistive fault current limiting device development using QMG HTC bulk superconductor", IEEE Trans. Appl.Superconduct., Vol. 9, No. 2, p. 1312, 1999 https://doi.org/10.1109/77.783543
  6. S. H. Lim, Y. S. Cho, H. S. Choi, and B. S. Han, "Improvement of current limiting capability of HTSC elements in hybrid type SFCL", IEEE Trans. on Appl. Supercond., Vol. 17, No. 2, p. 1807, 2007 https://doi.org/10.1109/TASC.2007.899246
  7. K. B. Park, J. S. Kang, B. W. Lee, I. S. Oh, H. S. Choi, H. R. Kim, and O. B. Hyun, "Quench behavior of YBaCuO films for fault current limiters under magnetic field", IEEE Trans. on Appl. Supercond., Vol. 13, No. 2, p. 2092, 2003 https://doi.org/10.1109/TASC.2003.812988
  8. K. Tekletsadik, M. P. Saravolac, and A. Rowley, "Development of a 7.5 MVA superconducting fault current limier", IEEE Trans. Appl.Superconduct., Vol. 9, No. 2, p. 672, 1999 https://doi.org/10.1109/77.783385
  9. T. Onishi, M. Kawasumi, K.-I. Sasaki, and R. Akimoto, "An experimental study on a fast selfacting magnetic shield type superconducting fault current limiter", IEEE Trans. Appl. Superconduct., Vol. 12, No. 1, p. 868, 2002 https://doi.org/10.1109/TASC.2002.1018538
  10. T. Matsumura, T. Uchii, and Y. Yokomizu, "Development of flux-lock-type current limiter with high-Tc superconducting element", IEEE Trans. Appl. Superconduct., Vol. 7, p. 1001, 1997 https://doi.org/10.1109/77.614676
  11. S. H. Lim, B. S. Han, and H. S. Choi, "Operational characteristics of flux-lock type SFCL using series resonance", Trans. EEM, Vol. 6, No. 4, p. 159, 2005 https://doi.org/10.4313/TEEM.2005.6.4.159
  12. S. H. Lim, H. S. Choi, and B. S. Han, "Fault current limiting characteristics due to winding direction between coil 1 and coil 2 in a flux-lock type SFCL", Phys. C, Vol. 416, p. 34, 2004 https://doi.org/10.1016/j.physc.2004.08.019