Abstract
The SCR in Static Transfer Switch (STS) is used for reliability improvement of important load's power supply in industry field. However an average of 2% fault in thyristor(SCR) occurs, so that the attached mechanical switch is paralleled with SCR's both end points and SCR operates only during the $12{\sim}208$[mS] before operation of the mechanical switch. Also, an ISC (Ideal State Conditioning Interlock Device) - STS system that two power supply paths may not be thrown at the same time is developed to remove the overlap section perfectly when a short or earth fault is generated in one system. This method has reduced the fault rate remarkably through the reduction of SCR's fatigue degree by using SCR in conversion operation corresponding to 0.89 times a year. Also, in case of fault generations, it does not affect to supply power to the load, therefore it contributes to the promotion of reliability in the power supply.
본 논문은 산업현장에서 중요부하에 안정적인 전원공급을 하기 위하여 설치한 Static Transfer Switch (STS)의 사이리스터(SCR)가 평균 2%대의 고장으로 문제가 되고 있어 이를 방지하고자 SCR 양단에 기계적인 접점스위치를 병렬로 연결시키고 SCR은 병렬스위치가 동작 가능한 구간인 $12{\sim}208$[mS] 구간에만 기능을 수행하도록 구성하였다. 또한 두 개의 입력 중 어느 한쪽이 단락 또는 지락 사고가 발생되더라도 다른 한쪽의 경로와 부하에 영향을 주지 않도록, 두 개의 입력이 동시 투입되는 시간을 차단하는 ISC (Ideal State Conditioning Interlock Device) - STS 시스템을 제안하였다. 이 제안으로 년간 0.89회의 전환 동작 시에만 SCR이 역할을 하고 전환시점 이후에는 병렬스위치가 전원공급계통의 역할을 함으로서 SCR의 피로도를 현저히 감소시켜 고장률을 감소시킬 뿐만 아니라 고장이 발생된 경우라도 부하에는 영향을 미치지 않아 중요부하의 전원공급에 대한 신뢰성을 높이는데 기여할 수 있다.