A Study on the Performance Evaluation of the Hybrid Ventilation System for Small Apartment Houses

소형 공동주택의 하이브리드 환기시스템 성능실험 연구

  • 전주영 (대한주택공사 주택도시연구원) ;
  • 김길태 (대한주택공사 주택도시연구원) ;
  • 이종성 (대한주택공사 주택도시연구원) ;
  • 김상희 (대한주택공사 주택도시연구원)
  • Published : 2008.10.10

Abstract

From Feb. 2006, the ventilating systems with air exchange rate of over 0.7times/hour are installed at the apartment houses (over 100 units). Installation cost and maintenance cost are very important factors for ventilating system because consumers have to pay the expenses of that system. Especially small apartment needs more considerations because small apartment is comparatively the economically weak part. The purpose of this study is to the performance evaluation of the hybrid ventilation system for small apartment houses. Hybrid system 1 consists of natural ventilation system and duct type exhaust diffusers. Hybrid system 2 has natural ventilation system and toilet exhaust system with static pressure fan. Infiltration of test apartment houses with ventilation system is under 0.1 times/hour. Mean air age of hybrid system 1 is 1.52 hours and hybrid system 2 is 1.42 hours. Mean ventilation effectiveness of hybrid system 2(93%) is higher than that of hybrid system 1(81%).

Keywords

References

  1. 2006, The rule for a criterion of building facilities, MOCT
  2. Won, J. S., et al, 2007, An evalution of performance of hybrid ventilation system using the balcony space in apartment housing, Journal of Architectural Institute of Korea, Vol. 23, No. 5, pp. 187-194
  3. Kim, O., et al, 2007, A study on the pPerformance of hybrid ventilation system in highrise apartment houses, Proceedings of the SAREK Winter Annual Conference, pp. 113- 118
  4. Yi, S. H., 2006, A study of hybrid ventilation system applying to an apartment house, Proceedings of the SAREK Summer Annual Conference, pp. 1137-1143
  5. Hwang, J. H., et al, 2006, A prediction of hybrid ventilation system performance in apartment house, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 18, No. 7, pp. 541-548
  6. Kim, S. J., et al, 2006, Analysis of indoor air and thermal environment with hybrid ventilation system during summer, Proceedings of the SAREK Summer Annual Conference, pp. 387-392
  7. Nam, J. W., et al, 2006, The analysis of energy performance of the hybrid ventilation system in multi-unit residential building, Proceedings of the SAREK Winter Annual Conference, pp. 481-486
  8. 2006, Interpretation for standard of the ventilation facilities in the apartment and buildings for a crowd, MOCT
  9. 1991, KS F 2603, The method to measure indoor ventilation, Korean Industrial Standard
  10. 1991, Ventilation for Acceptable Indoor Air Quality, ASHRAE Standard