DOI QR코드

DOI QR Code

Dependence of the Partial Discharge Characteristics of Ultra-high Voltage Cable Insulators on the Measuring Temperature

  • Shin, Jong-Yeol (Department of Car Mechatronics, Sahmyook University) ;
  • Park, Hee-Doo (Department of Disasters Prevention Equipment, Kangwon National University) ;
  • Lee, Hyuk-Jin (Department of Electrical Engineering, Kwangwoon University) ;
  • Lee, Kang-Won (Department of Electrical Engineering, Kwangwoon University) ;
  • Kim, Won-Jong (Department of Electrical Engineering, Kwangwoon University) ;
  • Hong, Jin-Woong (Department of Electrical Engineering, Kwangwoon University)
  • 발행 : 2008.10.31

초록

Cross linked polyethylene (XLPE) insulators are used as insulation in ultra-high voltage electric power cables. This study investigated the electrical properties of XLPE at different temperatures. The electrical properties of the changing tree phenomenon was examined as a function of temperature applied to the electrical conductors by measuring the partial discharge at $25^{\circ}C$ to $80^{\circ}C$ and applied voltages to the electrodes ranging from 1 kV to 40 kV. The activity of the partial discharge was examined at various temperatures using the K-means distribution. The results revealed the specimen at $80^{\circ}C$ to have the lowest inception voltage and breakdown voltage. In addition, the core of clusters was moved $0^{\circ}$ and $180^{\circ}$ at the positive region and $180^{\circ}$ and $360^{\circ}$ in the negative region in the K-means. The distribution of clusters was concentrated on the inception condition and spread out widely at the breakdown voltage.

키워드

참고문헌

  1. S. Matsumoto, 'Recent technology of sensing, monitoring, diagnosis and maintenance for aged electric power and energy system', Trans. on IEEJ, Vol. 126-B, No. 6, p. 574, 2006
  2. T. Okamoto and T. Tanaka, 'Auto-correlation function of PD pulses under electrical treeing degradation', IEEE Trans. on Dielectrics EI, Vol. 2, No. 5, p. 857, 1995 https://doi.org/10.1109/94.469979
  3. IEC Publication 270, 'Partial Discharge Measurement', 2nd Edition, 1981
  4. T.-Y. Kim, B.-C. Ahn, H.-J. Lee, D.-G. Byun, and J.-W. Hong, 'The analyswas of partial discharge using k-means on ignition coil', CMD 2006, p. 160, 2006
  5. A. Contin, M. Cacciari, and G. C. Montanari, 'Estimation of Weibull Distribution Parameters for Partial Discharge Inference', 1994 Annual Report IEEE CEIDP, p. 71, 1994
  6. E. Gulski, 'Digital analysis of partial discharges', IEEE Trans. on Dielectrics EI, Vol. 2, No. 4, p. 822, 1995 https://doi.org/10.1109/94.469977
  7. R. A. Johnson and D. W. Wichern, 'Applied multivariate statistical analysis', Prentice Hall, p. 573, 1992
  8. R. O. Duda, P. E. Hart, and D. G. Stork, 'Pattern Classification', John Wiley & Sons Ltd., p. 517, 2001
  9. T. Tanaka, 'Internal partial discharge and material degradation', IEEE Trans. DEI, Vol. 21, No. 6, p. 899, 1986
  10. T. Shimakage, K. Wu, T. Okamoto, and Y. Suzuoki, 'Life-cycle-cost evaluation on degradation diagnosis for cables', Trans. on IEEJ, Vol. 124-A, No. 3, p. 277, 2004
  11. K. S. Cho, K. W. Lee, W. J. Kim, J. Y. Shin, and J. W. Hong, 'Partial discharge diagnosis of interface defect by the distribution statistical analysis', J. of the KIEEME(in Korean), Vol. 21, No. 4, p. 348, 2008 https://doi.org/10.4313/JKEM.2008.21.4.348

피인용 문헌

  1. Technical Relevance of Epoxy/Clay Nanocomposite with Organically Modified Montmorillonite: A Review vol.55, pp.13, 2016, https://doi.org/10.1080/03602559.2016.1163593