Analytical study on resisting moment of concrete pole installed in sloped ground

콘크리트 전주의 경사지 저항 모멘트에 관한 해석 연구

  • Published : 2007.08.31

Abstract

In this study, for the purpose of estimating the resisting moment of sloped ground based on level ground fall down safety equation in design specification, compute it depends on penetration depth of concrete pile applying modulus of foundation about the angle of internal friction, cohesion, unit weight of soil, classes of the ground, sandy or clay soil, and verify established study using L-Pile Plus13.8. Also, select four cases that characteristics of soil depending on the soil grade is considered and compute the 12m length concrete pile's resisting moment of the ground those angle is changing from $0^{\circ}{\sim}35^{\circ},\;step\;5^{\circ}$. In the result, identify that the resisting moment of ground decreases depending on ground slope. Thus, increasing of penetration depth is required.

본 연구에서는 설계기준에 제시된 평지 전도 안전율 계산식을 바탕으로 경사지에서의 지반의 저항모멘트를 산정하기 위해 범용 해석 프로그램 L-Pile Plus13.8을 사용하여 기존 연구와 검증하였다. 지반의 일반적인 토질상태별 특성을 고려한 내부마찰각, 점착력, 흙의 단위중량, 지반종류, 사질토 및 점성토 지반계수를 적용하여 각 전주의 근입 깊이에 따른 지반의 저항모멘트를 산정하였다. 또한 토질등급에 따른 토질의 상태별 특성이 고려된 4가지 경우를 선정하여 12m 중하중용 전주를 대상으로 경사지의 경사각을 $0^{\circ}{\sim}35^{\circ}$까지 $5^{\circ}$씩 증가시켜 지반의 저항모멘트를 산정하였다. 그 결과 경사지 경사각에 따른 저항모멘트가 감소하는 것을 확인 할 수 있었으며 그에 따른 경사지의 근입 깊이 증가가 필요한 것으로 판단된다.