An Evaluation Method for Short-Term Ratings of Double-Circuit Overhead Transmission Lines

2회선 가공송전선의 단시간정격에 관한 평가방법

  • 김성덕 (한밭대학교 전기.전자.제어공학부) ;
  • 손홍관 (전기연구원 전력연구단) ;
  • 장태인 (한국전력공사 전력연구원 전력계통연구실)
  • Published : 2007.08.31

Abstract

This paper describes an analytical method to determine the short-term ratings to reliably operate the overhead transmission lines with double-circuit lines when faulting one circuit of the two. As linearizing the thermal equilibrium equation that represents the temperature characteristic of conductors, we show that the linear equation can be easily represented the over-current and it's temperature property during overloading the one line. Generally, it is well hewn that the short-term line ratings should be determined by considering both conductor life and dip. However, most power companies have their own different guides for the short-term ratings. Using the suggested method in this paper, it can be re-accessed the short-term ratings given in Kepco's overhead transmission lines constructed during the past three different periods. As a result, it is verified that the short-term ratings could be increased mil efficiently. Furthermore, it would be directly applied the given method to determine the short-term dynamic line ratings when occurring faults in one of the double-circuit lines, without doing my other actions for the current lines.

본 논문에서는 2회선 가공송전선에 대하여 2회선 중 1회선에 고장이 발생한 경우에 안전하게 운전할 수 있는 단시간정격을 결정하기 위한 해석적 방법을 기술한다. 도체의 온도특성을 나타내는 열평형방정식을 선형화 함으로써 이 선형방정식으로 1회선 선로에 과부하가 발생하는 동안 과전류와 그 온도 특성을 쉽게 표현할 수 있다. 일반적으로 단시간 선로정격은 도체의 수명과 이도를 동시에 고려하여 결정해야 한다는 것은 잘 알려진 사실이다. 그렇지만 대부분의 전력회사는 단시간정격에 대한 각자의 다른 지침을 갖고 있다. 이 논문에서는 제안된 방법을 사용하면 과거 3시기에 건설된 한국전력공사의 가공송전선에 규정된 단시간정격을 재평가할 수 있고, 그 결과 단시간정격을 효율적으로 증대시킬 수 있음을 확인하였다. 또한 이 방법은 2회선 선로 중 1회선에 고장이 발생할 경우에 기존 선로에 어떤 조치도 하지 않아도 단시간 동적송전용량을 결정하는데 직접 이용할 수 있을 것이다.

Keywords

References

  1. Draft standard for calculating the current-temperature relationship for bare overhead conductors, IEEE Standard P738, 1999
  2. J.S. Engelhardt, and S.P. Basu, 'Design, installation and field experience with an overhead transmission dynamic line rating system', Proceedings of IEEE, Transmission and Distribution, pp. 366-370, 1996
  3. 가공송전선의 전류용량, 일본 전기학회 기술보고 제660호, 1997
  4. 가공송전선용 전선 선정기준 - 1210, 한국전력공사, 2003
  5. IEEE General principles for rating electric apparatus for short-time intermittent or varying duty, IEEE Standard 96-1969
  6. Working paper on a proposed transmission relay loadability standard, SPCTF of the NERC Planning Committee, Dec. 2005
  7. 송전선로 지상고 기준 - 1020, 한국전력공사, 2003
  8. V.T. Morgan, 'Effect of elevated temperature operation on the tensile strength of overhead conductors', IEEE Trans. on Power Delivery, Vol. 11, No. 1, pp. 345-352, Jan. 1996 https://doi.org/10.1109/61.484034
  9. R.D. Findlay, D. Brocilo, and V.T. Morgan, 'Sensitivity analysis of aluminum conductor steel reinforced (ACSR) using historical permeability data from a single wire versus stranded steel core permeability data', IEEE Canadian Conference on Electrical and Computer Engineering, Vol. 2, pp. 906-909, 1998
  10. 가공선 이도 설계기준 - 1211, 한국전력공사, 2003
  11. 이도 설계 프로그램, Tower+, 한국전력공사, 2003

Cited by