DOI QR코드

DOI QR Code

Recommended Practice for a Reasonable Design Demand Factor and Analysis of Power Consumption Characteristics by loads in Hospitals

병원용 건물의 부하종별 전력소비특성 분석 및 수용률 기준 정립에 관한 연구

  • 유상봉 (용인송담대학 조명인테리어과) ;
  • 김세동 (두원공과대학 전기공학과)
  • Published : 2007.07.31

Abstract

It is increased electrical energy consumption with the development of intelligence society in hospitals and thus an energy conservation through efficient use of electricity became more important. This paper shows a reasonable design demand factor in hospitals, that was made by the systematic and statistical way considering actual conditions, such as investigated electric equipment capacity, peak power consumption, demand factor, etc., for 32 hospitals and 9 electrical design offices. In this dissertation, it is necessary to analyze the key features and general trend from the investigated data. It made an analysis of the feature parameters, such as average, standard deviation, median, maximum, minimun and thus it was carried the linear and nonlinear regression analysis.

병원용 건물과 같은 전력다소비 건물에서는 전력의 효율적 이용에 의한 에너지절감을 위해서 설계 단계부터 합리적인 전기설비 설계가 요청되고 있다. 본 연구에서는 병원용 건물 32개소를 선정하여 부하종류별 전력소비특성을 조사 분석하였고, 9개소의 전기설계사무소로부터 설계단계에서 적용하는 수용률값을 조사하였다. 조사된 자료의 전체 특징과 중심적인 경향을 알아 보기 위해서 평균값, 표준편차, 최대값, 최소값, 중앙값 등의 특징파라메터를 분석하였고, 회귀분석을 통한 선형적인 방법과 비선형적인 방법으로 그 경향을 확인하였다. 그 결과 합성 수용률 평균값은 47.5[%]이었으며, 전력용변압기는 용량에 있어서 많은 여유를 가지고 있는 것으로 나타났다. 이를 토대로 변전 설비용량의 합리적인 설계를 위하여 부하종별 수용률 기준(안)을 제시하였고, 변전설비용량 산정에 필요한 자료를 데이터베이스화하였다.

Keywords

References

  1. 김세동, 업무용빌딩의 전력소비특성을 고려한 수용률/부등률의 적용에 관한 연구,Vol.16, No.6, pp.74-79, 2002
  2. 지철근 외, 건축전기설비설계기준, 건설교통부, 2000
  3. 대한전기협회, 내선규정전문위원회, 최신개정판, 내선규정, 2006
  4. 김세동 외, 업무용건물의 전력소비특성을 고려한 수용률기준 제정 연구에 관한 최종보고서, 한국조명전기설비학회, 2004