초록
The purpose of this study was to analyze the difference of thermal sensation by radiant floor heating as ecological design element. The experimental investigations were carried out in climate chamber, and subjects were 34 college-age females in good health. The experimental variable was radiant heat by floor heating, and experimental controlled conditions were indoor temperature, relative humidity, and air velocity in climate chamber and clothing value and activity of subjects. The results are as follows. (1) Indoor temperature($21{\pm}0.5^{\circ}C$) in climate chamber were maintained as controlling. Clothing values of the subjects were controlled as average 0.73 clo. In the floor heating-off, globe temperature was average $23.2^{\circ}C$(22.4~24.1), but in the floor heating-on, globe temperature was average $24.8^{\circ}C$(23.0~25.5). (2) In the floor heating-off, thermal sensation rating was average -1.03(slightly cool), in the floor heating-on, thermal sensation rating was average +1.03(slightly warm). (3) There were the differences of thermal sensation by radiant floor heating although indoor temperatures were maintained in an equal state. (4) The thermal sensation rating was tending upward according as the globe temperature was getting higher.