DOI QR코드

DOI QR Code

A Study of Life Prediction Assessment of T/L 36,000 Ibs Porcelain Insulators

송전용 36,000 lbs 자기애자의 수명 예측 연구

  • Published : 2007.07.01

Abstract

36,000lbs porcelain insulators of D-1995, D-1997 and D-2002 investigated mechanical and electrical qualities, where is process of using in the Korea 154 kV transmission lines. It analyzes the cause of the elapse of a year aging of the transmission insulators. Weibull distribution function, product quality and uniform quality, etc. investigated for prediction to extant life of insulator. It calculate change as statistical elapse of a year through product qualities of used insulator and new insulator, uniform equality and uniformity of insulator. In case of D-1995 year used insulator, it decided to badness decline index k by 0.0237, badness quality index by 1.0 and 3.0. Result of extant confidence life Ym was calculated that remain each 4 yens and 0.7 yens that uniformity index is considered. Extant life of D-1997 and D-2002 insulators Predicted by about 40 years.

Keywords

References

  1. '2000년 송전설비 고장분석 및 대책자료' 1999년-2000년 통계 자료, 한국전력공사
  2. '송전용 현수애자의 성능확인 및 특성시험 분석', 연구기획조사사업, 한국전력공사, 전력연구원, 1999
  3. '250 mrn 볼소켓형 현수애자', ES 131-540-543, 한전 구매시방서, 1995
  4. K. Niihara, R. Morena, and D. P. H. Hasselman, 'Evaluation of KIC of brittle solids by the indentation method with low cracks-to-indent ratio', J. Mater. Sci. Lett., Vol. 1, p, 13, 1982 https://doi.org/10.1007/BF00724706
  5. '초고압(400 kN)용 내장애자 국산화 개발', 한국전력공사, 고려애자공업(주), 최종보고서, 2002
  6. 최인혁, 최장현, 이동일, 최연규, '송전용 자기 재 현수애자의 원료변화에 따른 특성 연구', 전기전자재료학회논문지, 17권, 4호, p. 390, 2004
  7. '고신뢰성 자기재 배전용 현수애자 개발', 한국전력공사, 한국전기연구소, 최종보고서, 1996
  8. '송전용 애자의 신뢰성 평가 연구', 한국전력공사, 전력연구원, 2006
  9. T. Iwama, K. Kito, K. Naito, and T. Irie 'Ultra-high strength suspension insulators and insulator string assembles for URV transmission line', IEEE. Transactions on Power Apparatys and System., Vol. PAS-101, No. 10, 1982
  10. K. Naito, R. Matsuoka, T. Irie, and K. Kondo, 'Test method and results for recent outdoor insulation in Japan', IEEE Transactions on Dielectrics and electrical Insulation, Vol. 6, No. 5, 1999
  11. '자기 애자 애관의 파괴 강도에 대하여', NGK Review 30, 1970
  12. '절연 열화 진단 기술', 일본전기평론, p. 52, 1990
  13. 'がいし', 日本電氣學會, p. 87, 1984