Abstract
In the case that an overcurrent flows through in electrical wire due to short-circuit or overload, the wire can be fused, thereby causing an electrical fire. In the present article the characteristics of the fusing current of an electrical wire have been studied to discriminate between short-circuit and overload. In the experiment the fusing time was measured as the currents determined by Preece's equation were supplied to bare wires of various diameter. As the results of experiment, the measured fusing currents well satisfied the Onderdonk's equation. By comparing the measured results and the short current the IEC recommends, it is shown that the variable to determine the short current for a bare copper wire, k is appoximately 300. The fusing current of an electrical wire which becomes a short circuit within 5sec can be expressed as a function of diameter based on the value of k. Consequently, the equation for the fusing current provides a criterion to discriminate between short-circuit and overload.
단락 또는 과부하에 의하여 전선에 과전류가 흐를 경우 전선은 용단되고 이것은 전기화재를 발생시킬 수 있다. 본 논문에서는 단락과 과부하를 판별하기 위하여 전선의 용단전류 특성을 연구하였다. 실험에서는 여러 가지 직경의 나전선에 프리스 식에 근거하여 정한 용단전류를 공급하고 용단시간을 측정하였다. 실험 결과 측정한 용단전류는 온더동크 식을 잘 만족하였다. 측정결과와 국제전기기술표준에서 제시하는 단락전류를 비교하여 나동선에 대한 단락전류를 결정하는 변수 k값이 약 300임을 보였다. 이 값에 근거하여 5초 이내에 단락되는 전선의 용단전류를 직경의 함수로 표현할 수 있다. 결과적으로 이 용단전류의 식은 단락과 과부하를 판별할 수 있는 기준을 제공한다.