Saturation Characteristic of Iron Core Dependent on Fault Angle in a Flux-Lock Type SFCL

자속구속형 초전도 사고전류제한기의 사고각에 따른 철심의 포화특성

  • Published : 2007.12.31

Abstract

The fault current limiting characteristics of a flux-lock type superconducting fault current limiter(SFCL) according to fault angles were investigated. From the electrical equivalent circuit with the magnetization branch, the inner magnetic flux of this SFCL due to fault angles was induced and its effect on the limited fault current was analyzed. From the fault current limiting experiments, the exciting current, which described the saturation of the iron core, was calculated and its dependence on the fault angle was analyzed. Before the fault happened, the exciting current did not happen, that it kept zero value. However, after the fault happened, the exciting current flowed and, the exciting current in case of the additive polarity winding showed higher value than for the case of the subtractive polarity winding. The analysis results were compared with the experimental ones, and experimental results agreed with the analysis ones.

본 논문에서는 사고각에 따른 자속구속형 초전도 사고전류제한기의 사고전류제한 특성을 분석하였다. 이를 위해 자화가지를 포함한 등가회로로부터 사고각에 따른 자속구속형 초전도 사고전류제한기의 철심내부자속을 유도하였으며 사고전류에 미치는 영향을 분석하였다. 사고전류제한 실험을 통해, 철심의 포화와 관련한 여자전류를 유도하였으며 사고각에 따른 변화를 분석하였다. 사고전에는 발생되지 않았지만 사고가 발생함과 동시에 여자전류크기가 증가하였으며 특히, 자속구속형 초전도 사고전류제한기를 가극결선한 경우가 감극결선한 경우보다 보다 크게 증가되는 것을 확인할 수 있었다. 등가회로로부터 분석한 결과와 실험결과는 일치되는 것을 확인할 수 있었다.

Keywords

References

  1. V. D. Pham, Y. Laumoud, T. Verhaege, Fevrier, M. Collet, M. Bekhaled, 'Towards The Superconducting Fault Current Limiter, IEEE Trans. on Appl. Supercond, Vol. 6, pp. 801-808 April 1991
  2. Lin Ye, LiangZhen Lin, Klaus-Peter Juengst, 'Application Studies of superconducting Fault Current Limiters in Electric Power Systems', IEEE Trans. on Appl. Supercond., Vol. 12, No. 1, pp.900-903, Mar., 2002 https://doi.org/10.1109/TASC.2002.1018545
  3. Sung-Hun Lim et al., 'Current limiting characteristics of flux-lock type High-Tc superconducting fault current limiter with control circuit for magnetic field', IEEE Trans. on Appl. Supercond., Vol. 13, No. 2, pp.2056-2059, June, 2003 https://doi.org/10.1109/TASC.2003.812984