DOI QR코드

DOI QR Code

Protection Effects Associated with the Conditions for the Installations of SPDs

SPD의 설치조건이 보호효과에 미치는 영향

  • Published : 2006.02.28

Abstract

This paper presents the protection effect of surge protective devices(SPDs) according to the conditions of installations. To propose the effective protection measures of information and communication equipments against lightning surges, actual-sized experiments in relation to the protection effects on the positions of installations of SPDs, the length of branch circuit, the wiring methods, and the materials of conduit, were conducted. The effective method of protecting information and communication equipments from lightning surges is to install SPDs in the vicinity of input terminals of each electronic equipments to be protected. The wiring method of connecting an SPD minimizing the length of leads is desirable when point-to-point wiring is to be used.

이 논문은 서지보호기의 설치조건에 따른 보호효과에 대하여 기술하였으며, 뇌서지로부터 정보통신설비를 효과적으로 보호하는 설치기법을 제안하기 위해 서지보호기의 보호효과에 미치는 설치위치, 분기회로의 길이, 배선방법, 전선관 재료의 영향에 대해서 실규모 조건에서의 실험을 수행하였다. 그 결과, 보호하고자 하는 각각의 전자기기의 입력단에 서지보호기를 설치하는 것이 효과적이며, 선간에 서지보호기를 설치할 때는 접속선의 길이가 최소가 되도록 하는 배선방법이 효과적이다.

Keywords

References

  1. B. Richter, 'Surge Protective Devices for Low-Voltage Power Distribution Systems, -The New IEC-Standard and First Experience with It', Proc. 23rd ICLP, Paper No.7C-1, pp.764-767, 1998
  2. R. B. Standler, 'Protection of Electronic Circuits from Overvoltages', John Wiley & Sons, Inc., First edition, New York, pp.3-33, 1989
  3. 이복희, 이동문, 강성만, 엄주홍, 이승칠, '정보통신용 뇌 서지 보호장치의 효과적인 설치기법', 한국조명.설비 학회 논문지, Vol.16, No.5, pp.90-96, 2002
  4. M. B. Marz, S. R. Mendis, 'Protecting load devices form the effects of low-side surges', IEEE Trans., Vol. 29, No. 6, November/December 1993
  5. Task Force Report, 'Secondary(low-side) surge in distribution transformers', IEEE Trans., Vol. 7, No 2, April 1992
  6. R. P. O'Riley, Electrical Grounding, International Thomson Publishing Company, 5th Edition, pp.60-79, 1999
  7. 이승칠, '정보화 건축물의 뇌보호시스템', 인하대학교 대학원 졸업논문, pp.101-108, 2002. 2, ('A Lightning Protection System for Information-oriented Structures')