A Study on the Active Noise Control in Duct

닥트내 소음의 능동제어에 관한 연구

  • 이채봉 (동서대학교 정보시스템공학부)
  • Published : 2006.07.01

Abstract

There have been experiments dealing with the possibility of the actualization of the ANC system by means of operating the DSP adaptation filter. This filter is composed of various filters(including X-LMS algorithm, Filter-U algorithm, and Full-Feedback-Filter-U algorithm) that use ventilation fans and loudspeakers as a primary source in a circular duct as an experimental device. In this operation, the ANC system using the X - LMS algorithm was found to be more effective in reducing noise than without such system. When applying the input signal of the DSP board Full Feedback-Filtered-U algorithm system while having in mind that the additionally installed second control signal was gone through feedback and mixed into the detection microphone installed near the ventilation fan when using the first ventilation fan, the system was not emitted, but maintained stable during the operation of the control filter. At this point, noise tended to decrease at a maximum of l0dB compared to other algorithms at the frequency band of 170-250Hz.

원형관의 닥트를 사용하여 1 차원 구동원으로써 라우드스피커와 환기용 팬을 사용하여 각종 알고리즘인 X-LMS 알고리즘과 Filtered-U 알고리즘 그리고 Full-Feedback Filtered-U 알고리즘으로 구성한 DSP 적응필터를 작동시켜 닥트에 적용할 수 있는 능동소음 제어시스템 실현의 가능성에 대하여 여러 가지 실험을 하였다. 1 차 구동원을 환기용 팬을 사용할 때 2 차 제어용 신호가 환기용 팬에 가까이 있는 탐지 마이크로폰에 혼입되는 현상을 고려한 Full-Feedback Filtered-U LMS 알고리즘을 능동제어 시스템에 적용하여 적응제어 필터를 작동하면 시스템이 발산되지 않고 안정상태에서 주파수 범위 170-250Hz 사이에서 다른 알고리즘에 비하여 소음량이 최대치에서 10dB 정도 감소되었다.

Keywords