DOI QR코드

DOI QR Code

공동주택 화재 경보음 전달특성과 개선방안 고찰

An Study on the Sound Attenuation and the Improvement in Hearing Condition of Fire Alarm Device in Apartment Buildings

  • 이민주 (서울시립대학교 건축음환경연구실) ;
  • 윤명오 (서울시립대학교 건축학부) ;
  • 김명준 (서울시립대학교 건축학부)
  • 발행 : 2006.06.01

초록

In many fire emergencies, the auditory fire alarm signals are very important to save the occupant's life. But as the sound insulation of building elements has been improved, it is more difficult for occupant to recognize the fire alarm signals when the audible fire alarm worked. This is the first study to show the sound attenuation of audible fire alarm device in apartments. We measured and analyzed the sound attenuation level in seven units. The result showed that it was not sufficient to detect the sound from the fire alarm device in bedrooms. Whether the fire alarm device worked or not, the differences of sound level in bedrooms were below 1$\sim$10 dBA. To give the minimum sound level 60 dBA in bedrooms, the proper sound levels from alarm device installed in livingrooms were suggested using computer simulation.

키워드

참고문헌

  1. Ministry of Government Administration and Home Affairs., 2000, 'Fire Statistics Report(2001), , 2001, 'Fire Statistics Report(2002),' 2002, ' Fire Statistics Report (2003)'
  2. Ministry of Government Administration and Home Affairs., 1998, '1997 Fire Statistics Report,' pp. 61/1999, '1998 Fire Statistics Report,' p, 49
  3. Dorothy Bruck, 2001, 'The Who, What, Where and Why of Waking to Fire Alarms,' Fire Safety Journal, Vol, 36, pp. 623 - 639 https://doi.org/10.1016/S0379-7112(01)00025-X
  4. Wong, L. T. and Leung, L. K., 2005, ' Minimum Fire Alarm Sound Pressure Level for Elder Care Centrs,' Building and Environment, Vol. 40, pp. 125 -133 https://doi.org/10.1016/j.buildenv.2004.05.004
  5. Dorothy Bruck, 1999, 'Non-awakening in Children in Response to a Smoke Detector Alarm, ' Fire Safety Journal, Vol. 32, pp. 369 - 376 https://doi.org/10.1016/S0379-7112(98)00035-6
  6. Donald Arthur Robinson, 1988, 'Sound Attenuation in Buildings : Implications for Fire Alarm System Design,' Fire Safety Journal, Vol. 14 , pp. 5 -12 https://doi.org/10.1016/0379-7112(88)90040-9
  7. Kim, J. S., 2004, 'Architectural Acoustics Design,' Sejinbook, pp. 487-500
  8. Kim, J. S., 2004, 'Architectural Acoustics Design,' Sejinbook, pp. 487-500
  9. Kim, J. S., 2004, 'Architectural Acoustics Design,' Sejinbook, pp. 487-500
  10. Ryu, J. K., Jeon, J. Y. and Kim, H. S., 2005, 'Development of Noise Annoyance Scale and Criteria of Residental Noise through Auditory Experiments,' Transactions of the Korean Society for Noise and Vibration Engineering, Vol. 15, No. 3, pp, 904 - 910 https://doi.org/10.5050/KSNVN.2005.15.8.904