An Experimental Study on the Load Delivery Characteristics of Hybrid Energy System with Geothermal and Solar Heat Sources

지열-태양열원 복합시스템의 부하추종특성에 관한 실험 연구

  • Hwang, In-Ju (Fire&Engineering Services Research Dept., Korea Institute of Construction Tech.) ;
  • Woo, Nam-Sub (Graduate School of Mechanical Engineering, Sungkyunkwan University)
  • 황인주 (한국건설기술연구원 화재및설비연구부) ;
  • 우남섭 (성균관대학교 기계공학과 대학원)
  • Published : 2006.12.01

Abstract

The objective of the present study is to investigate the load delivery characteristics of a hybrid-renewable energy system with geothermal and solar heat sources for hot water, heating and cooling of a residential house in Korea. The hybrid energy system consists of ground source heat pump of 2 RT for cooling with a 150 m vertical U-bend ground heat exchanger, solar collectors of 4.8 m2 and gas fired backup boiler. The averaged coefficient of performance of geothermal module during cooling and heating seasons are evaluated as about 4.5 and 3.8, respectively.