Abstract
This paper presents assessment of possibility on the human risk for the electromagnetic field of unbalanced two coupled three-phase transmission line using fuzzy theory. Three phase load flow program was developed which employed a Newton-Raphson method as a tool to analyze system unbalanced. This research presents a method of handling two coupled three phase transmission system unbalance analysis and unbalanced power demand as a function of voltages. As the results of case study, in case of 345[kV] T/L, the electric field intensity was 10.9540[kV/m], magnetic field intensity was 0.2567[G] in severest case. The results showed that the membership of a proposition fuzzy '10.9540 [kV/m] is hazardous' is 0.6349. As the analytic results using the fuzzy qualifier term, the membership in case of very false is 0.1379 and fairly false is 0.6124, respectively. In assessment of fuzzy measure possibility for the electromagnetic field, this paper used probability of fuzzy arid measure of fuzziness technique.