스팀 에젝터에 의한 강제 증발 방식의 냉각 특성에 관한 연구

Study on Cooling Charcteristics of Forced Evaporation by using Steam Ejector

  • 손호재 (거제대학 메카트로닉스계열) ;
  • 이윤환 (경상대학교 정밀기계공학과) ;
  • 김영근 (경상대학교 정밀기계공학과) ;
  • 정효민 (경상대학교 기계항공공학부.해양산업연구소)
  • 발행 : 2006.05.31

초록

This study shows a water cooling system by using a steam ejector and jet condenser to drop the temperature of the water by about $5^{\circ}C\;from\;25^{\circ}C$ or higher. In this research, to replace the present water cooling system, we focused on a water cooling system by latent heat of evaporation, thus this system needs a vacuum pressure to evaporate the water in enclosed tank. The water cooling effects are depended on the vacuum pressure in the enclosed tank, and the cooling water is generated by latent head of evaporation. As the experimental results, the absolute vacuum pressure obtained was about $5{\sim}8$ mmHg using a steam driven ejector with jet condenser.

키워드