Effect of Positive Pressure Ventilator Tilting Angle on the Flame Suppression and Smoke Density

Positive Pressure Ventilator 경사각 변화에 의한 화염억제 효율과 연기농도 변화

  • Published : 2006.12.31

Abstract

The experiment applied Positive Pressure Ventilation to rapidly exhaust heat and smoke inside the construction in the fire was done. Changes of heat discharge and smoke density were measured, with the various blowing condition like a fan tilting angle to find the effect of the parameter. Experimental apparatus were with PPV and water mist system for better efficiency, and investigate the effect of heat discharge and smoke removal. In the experiment, flame temperature has decreased when PPV was applied. Smoke density, generated from fire also decreased dramatically and the efficiency showed the highest rate at $0^{\circ}$ tilting angle. In addition, combination of PPV and water mist system highly improved the efficiency of evacuation on heat and smoke density, clearly was influenced by the tilting angle.

화재시 구조물 내부의 열 및 연기를 급속하게 배기시키기 위하여 Positive Pressure Ventilation 방식을 적용하였으며, 이의 적용에 따른 열 배출과 연기농도의 변화를 측정하였고, 송풍기의 경사각 등 송풍조건의 변화에 따른 영향을 측정하였다. 또한 화염억제 효율증대를 위하여 PPV에 미세물분무 시스템을 결합하여 열 배출과 구조물 내부 연기제거 효과를 측정하였다. PPV 방식의 적용에 따라 화염주위의 온도가 급격히 낮아졌으며, 경사각의 영향이 큰 것으로 나타났다. 화재시 발생되는 연기의 농도도 PPV의 적용에 의해 크게 감소시킬 수 있었으며, 본 실험에서는 경사각 $0^{\circ}$에서 가장 높은 효율을 나타내었다. 한편, PPV와 함께 미세물분무를 적용한 경우 열 및 연기농도의 저감효과가 더욱 크게 나타났으며, 이 경우에도 경사각의 영향이 크게 나타났다.

Keywords

References

  1. Mittendorf, J., 'Positive Pressure Training Manual of Tempest', Tempest Tech. Co.(1992)
  2. Ertel, M. and Berk, G. C., 'Firefighting', The Goodheart-Willcox Company, Inc.(1998)
  3. www.firetactics.com
  4. Rimen, J., 'The Use of Positive Pressure Ventilation in Firefighting Operations', Fire Engineers, 60(206), pp.7-13(2000)
  5. Ingason, H. and Fallberg, R., 'Positive Pressure Ventilation in Single Medium-Sized Premises', Fire Technology, Vol. 38, pp.213-230(2002) https://doi.org/10.1023/A:1019825931076
  6. 鈴木弘昭, 敏 'ウャ-タ-ミスト(マイクロフォグ) による 消火に關する硏究開發(その1)', 消防檢定協會, Vol. 7, pp.20-23(1997)
  7. 신창섭, 이경덕, '방사특성 변화에 따른 미세물분의 소화특성', 한국화재.소방 학회, Vol. 15, No 4, 2001
  8. Victor, J. A., 'Use of Positive Pressure Ventilation (PPV) fans to Reduced the Hazards of Entering Chemically Contaminated Building', U.S. Army Edgewood Chemical Biological Center(ECBC), Report No. ECBC-TR-065(2000)
  9. Rimen, J., 'An Assessment of the Use of Positive Pressure Ventilation in Domestic Properties', FRDG Publication Number 17/96(1996)
  10. Tuomisaari, M., 'Smoke Ventilation on Operational Fire Fighting', VTT Publication 326, Technical Research Center of Finland(1997)
  11. 이경덕, '저압식 미세물분무 시스템의 소화성능 최적화와 첨가제의 영향', 공학 박사 학위논문, 충북대학교 안전공학과(2002)
  12. NFPA, 'The SFPE Handbook of Fire Protection Engineering'(2002)