Correlation between Insulation Diagnostic Test and AC Breakdown Test for 3.3 kV Class Induction Motor

  • Byun, Doo-Gyoon (Department of Electrical Engineering, Kwangwoon University) ;
  • Hong, Jin-Woong (Department of Electrical Engineering, Kwangwoon University)
  • Published : 2006.10.01

Abstract

The insulation diagnostic test and the AC breakdown test were performed under off-line using the 3.3 kV class induction motor which have been served for 10 years. These tests were conducted in means of nondestructive and destructive test. In this paper, we compared the correlation between the nondestructive and destructive test. Furthermore we setup an experimental condition with moisture and compared the insulation characteristics between moist and dry sample. From the results of the nondestructive and destructive test, it was found that the second AC current, which is the previous step of insulation breakdown, suddenly increased at a point of around 8.5 kV. The insulation breakdown of moist sample occurred at 12-14 kV, which is 4-5 kV lower than dry sample.

Keywords

References

  1. T. Kawamura and T. Tanaka, 'Diagnostics of power apparatus and cables', IEEJ Press, p. 10, 2003
  2. H. Xie, Y. Bo, and Y. Hao, 'Diagnosis of stator winding insulation of large generator', Proc. The 7th ICPADM 2003, p. 274, 2003
  3. S. C. Kim, J. B. Ok, M. J. Ahn, D. H. Park, and G. J. Lee, 'Electrical properties of organic/inorganic hybrid composites for insulation materials', Trans. EEM, Vol. 3, No.1, p. 9, 2002
  4. D. G. Byun, H. T. Shin, and J. W. Hong, 'Insulation diagnostic of high voltage electric power cable', Proc. 2002 Joint Conference of ACED & K-J Symposium and HVE, p. 651, 2002
  5. Y. Takezawa, J. Katagiri, and H. Shoji, 'Application of optical diagnosis to aged low-voltage cable insulation in nuclear plants', CEIDP 2004 Annual Report, p.290, 2004
  6. D. K. Bae, C. H. Kim, M. S. Pak, Y. C. Oh, J. S. Kim, C. G. Shin, J. U. Lee, M. J. Song, and W. S. Choi, 'A study on the electrical strength of insulating materials for high- Tc superconducting devices', Trans. EEM, Vol. 6, No.6, p. 294, 2005
  7. C. W. Park, J. H. Park, and M. J. Jeon, 'On-line fault diagnosis for three phase induction motor based on a statistical pattern recognition approach', Proc. KACC 2005, p. 453, 2005
  8. Y. Hao, G. Wang, Z. Jia, and H. Xie, 'Application of ultrasonic pulse-echo method to insulation condition diagnosis for large generators', IEEE Trans. On, Vol. 12, Iss. 1, p. 104, 2005
  9. D. G. Byun, B. K. Oh, D. S. Kang, and K. J. Lim, 'A study on the analysis of insulation aging for generator stator windings', Proc. the 36th the KIEE Summer Annual Conference, p. 2072, 2005
  10. D. Manna, A. Scavuzzo, G. Spoto, R. Candela, and P. Romano, 'A digital device for the diagnosis of insulation systems', CEIDP 2004 Annual Report, p. 481, 2004
  11. H. D. Kim and T. S. Kang, 'Analysis of partial discharge in high voltage motor model coils', Proc. the 36th the KlEE Summer Annual Conference, p. 2084, 2005
  12. T. Kawamura, N. Morita, and N. Sugimoto, 'Inspection and diagnosis for large motors', Fuji Review, Vol. 46, No.6, p. 43, 1991