DOI QR코드

DOI QR Code

6.6 kV급 고압전동기 고정자 권선의 절연열화 평가

Assessment of Insulation Aging in 6.6 kV Class High Voltage Motor Stator Windings

  • 김희동 (한국전력공사 전력연구원) ;
  • 김병한 (한국전력공사 전력연구원)
  • 발행 : 2006.11.01

초록

Prior to destructive testing, diagnostic tests were performed in ten high voltage motors. Diagnostic tests included polarization infer, ac current, dissipation factor$(tan{\delta})$ and partial discharge magnitude. The rewind of motet slater insulation at rated voltage is assessed by the results of these tests. After completing the diagnostic tests, the stator windings of motors were subjected to gradually increasing ac voltage, until the insulation punctured. No. 8 motor failed near rated voltage of 19.0 kV. The breakdown voltage of No. 4 motet was 7.0 kV which is lower that expected for good quality coils in 6.6 kV class motors. The failure was located in a line-end coil at the exit from the core slot. These two motors began operation in 1994. While testing No. 7 motor, flashover occurred between the stator winding and the stator frame at 15 kV. The relationship between the diagnostic test and the drop in insulation breakdown voltage was analyzed.

키워드

참고문헌

  1. I. M. Culbert, H. Dhirani, and G. C. Stone, 'Handbook to assess the insulation condition of large rotating machines', EPRI, EL-5036, Vol. 16, p. 3-25-3-28, 5-13-5-14, 1989
  2. G. C. Stone, 'Partial discharge diagnostics and electrical equipment insulation condition assessment', IEEE Trans. on Dielectrics and Electrical Insulation, Vol. 12, No. 5, p. 891, 2005 https://doi.org/10.1109/TDEI.2005.1522184
  3. G. Stone and J. Kapler, 'Stator Winding Monitoring', IEEE Industry Applications Magazine, p. 15, 1998
  4. H. Yoshida and K. Umemoto, 'Insulation diagnosis for rotating machine insualtion', IEEE Trans. on Electrical Insulation, Vol. EI-21, No. 6, p. 1021, 1986 https://doi.org/10.1109/TEI.1986.349018
  5. F. T. Emery, 'Partial discharge, dissipation factor, and corona aspects for high voltage electric generator stator bars and windings', IEEE Trans. on Dielectrics and Electrical Insulation, Vol. 12, No. 2, p. 347, 2005 https://doi.org/10.1109/TDEI.2005.1430403
  6. H. G. Sedding, R. Schwabe, D. Levin, J Stein, and B. K. Gupta, 'The Role of AC & DC Hipot Testing in Stator Winding Ageing', IEEE Electrical Insulation and Electrical Manufacturing & Coil Winding Conference, p. 455, 2003