DOI QR코드

DOI QR Code

A Study on the Frequency Control for Cheju HVDC linked System

제주 HVDC 연게 시스템의 주파수 제어에 관한 연구

  • 박종광 (한전 전력연구원 차세대전력기술그룹) ;
  • 최종기 (한전 전력연구원 차세대전력기술그룹) ;
  • 진성은 (한전 전력연구원 차세대전력기술그룹) ;
  • 김찬기 (한전 전력연구원 차세대전력기술그룹) ;
  • 한병성 (한전 전력연구원 차세대전력기술그룹) ;
  • 김경철 (한전 전력연구원 차세대전력기술그룹)
  • Published : 2005.03.01

Abstract

Cheju-Haenam HVDC link transmits electrical power up to 300[MW] Because of its size, HVDC system has a great potential for damping power system oscillations. This paper with the frequency control of the KEPCO HVDC system linking Haenam to Cheju island. Frequency control at Cheju island ensures that the island AC system frequency is maintained Performance are evaluated using a reduced Cheju network and a detailed model of the fm system modelled in the PST software. Transient oscillations for the 3 phase fault carried out with HVDC frequency control are well damped as the control parameters have been adjusted.

제주-해남 HVDC 시스템은 300(MW)까지 전력을 공급한다. 용량이 큰 HVDC 시스템은 전력계통의 동요를 댐핑하는데 적합하다. 본 논문은 해남과 제주도를 연결하는 HVDC 시스템의 주파수 제어를 다루었다. 제주도의 주파수 제어는 제주도 전력계통의 시스템 주파수를 일정하게 유지하는데 있다. PST프로그램으로 제주 전력계통을 축소 등가화 시키고, HVDC 시스템은 상세 모델링하여 성능 평가를 하였다. 적정 댐핑 계수를 유지하도록 HVDC주파수 제어기의 파라미터를 선정하였고, 3상 단락 사고시 제주 계통의 과도 동요현상은 시뮬레이션 결과 충분한 댐핑으로 안정되게 제어됨을 확인하였다.

Keywords

References

  1. Program manual, 'Power System Toolbox', Cherry Tree Scientific Software, 2004
  2. Graham Rogers. 'Power System Oscillations', Kluwer Academic Publishers, 2000
  3. P. Kundur, 'Power System Stability and Control', McGraw-Hill Inc., 1994
  4. PSS/E Program Operation Manual, Power Technologies Inc, Nov. 2001
  5. '교직 연계 계통의 안정 운용을 위한 협조제어 및 보호기술 향상연구', 최종보고서, 한전 전력연구원, 2002.5
  6. 김찬기, '제주-해남 HVDC 과도 특성 분석', 대한 전기학회지, 2000.9
  7. Haenam-Cheju HVDC Link Operation and Maintenance Manual, GEC Alstom, 1993
  8. J. A. Cadeow and H. R. Martens, 'Discrete-time and Computer Control System', Prentice-Hall Inc., 1970