Abstract

The air-side particulate fouling in the heat exchangers of HVAC applications degrades the performance of cooling capacity, pressure drop across a heat exchanger, and indoor air quality. Indoor and outdoor air contaminants foul heat exchangers. The purpose of this study is to investigate and to model the air-side particulate fouling characteristics of the heat exchangers using accelerated particle loading system. The main variables of the modeling equation are face velocity and dust concentration. The modeling equation shows good agreements with the experimental results at the face velocity of 0.5, 1.0, 1.5 m/s and the dust concentration of 1.28 and $3.84\;g/m^3$. It will be very useful to predict fouling characteristics such as variations of pressure drop and heat transfer capacity in finned-tube heat exchangers of air conditioners.

Keywords

References

  1. Webb, R. L., 1994, Principles of enhanced heat transfer, John Wiley & Sons Inc., p. 287
  2. Ahn, Y. C., Cho, J. M., Lee, J. K, Lee, H. U., Ahn, S. P., Youn D. H., Ha S. C., Kang, T. W., and Ock, J. H., 2003. An experimental study of the air-side particulate fouling of finned-tube heat exchangers of air conditioners by using accelerated particle-loading system, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 15, No. 10, pp. 802-808
  3. Siegel, J. A., 2002, Particulate fouling of HVAC heat exchangers, Ph. D. thesis, University of California, Berkeley, U.S.A
  4. Kern, D. Q. and Seaton, R. E., 1959, A theoretical analysis of thermal surface fouling, British Chemical Engineering, Vol. 14, No. 3, pp, 258-262
  5. Ahn, Y. C., Cho, J. M., Lee, J. K., Lee, H. U., Ahn, S. P., Youn D. H., and Kang, T. W. 2003. An Experimental Study of the Air-side Particulate Fouling in Fin-and-Tube Heat Exchangers of Air Conditioners, Korean Journal of Chemical Engineering, Vol. 20, No. 5, pp. 873-877 https://doi.org/10.1007/BF02697291
  6. Ahn, Y. C., Cho, J. M., Lee, J. K, Lee, H. U., Ahn, S. P., Youn D. H., Ha S. C., and Kang, T. W., 2003. Performance evaluation of heat exchangers due to air-side particulate fouling in the air conditioners, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 15, No. 6, pp. 447-453
  7. Korean Standard, KS C 9306, 2002, Air Conditioners
  8. Japanese Industrial Standard, JIS Z 8901, 1995, Test powders and test particles
  9. Bott, T. R., and Bemrose, C. R., 1983, Particulate fouling on the gas-side of finned tube heat exchangers, Journal of Heat Transfer, Vol. 105, pp. 178-183 https://doi.org/10.1115/1.3245538