Journal of Power System Engineering (동력기계공학회지)
- Volume 9 Issue 4
- /
- Pages.18-23
- /
- 2005
- /
- 2713-8429(pISSN)
- /
- 2713-8437(eISSN)
Study on the Performance of Total Heat Exchanger with Rotating Porous Plates
다공형 전열판의 회전에 의한 열교환시스템의 성능에 관한 연구(Ⅱ) - 전열판의 회전수 변환에 대하여 -
Abstract
The experimental investigation was carried out to evaluate the performance of air-to-air heat exchanger with rotating porous plates newly developed in this study. The rotating porous plates are mounted with an equal interval of 18 mm inside the heat exchanger where the hot and cold airs enter at opposite ends. When flowing in opposite directions by the separating plate installed in the center of the rotating porous plates, the airs give and receive the heat each other. The material of the porous plate is cooper and its thickness is 1.0 mm. Air flow rate is varied from 10 to 120 m3/h. From the experiment of air-to-air heat exchanger with the rotating porous plates, the heat exchange performance increased with the increase in RPM of the porous rotating discs at the conditions of the same air flow rate. The sensible heat exchange efficiency was maximum 60 to 70 percent, and enthalpy exchange efficiency 50 to 60 percent.
Keywords