Journal of Power System Engineering (동력기계공학회지)
- Volume 9 Issue 2
- /
- Pages.88-92
- /
- 2005
- /
- 2713-8429(pISSN)
- /
- 2713-8437(eISSN)
Thermal Performance Characteristics of Closed-Wet Cooling Tower
밀폐형 냉각탑의 열성능 특성에 관한 실험적 연구
- Sarker, M.M.A. ;
- Kim, E.P. ;
- Moon, C.G. ;
- Yoon, J.I.
- Published : 2005.05.31
Abstract
The experiment of thermal performance about closed-wet cooling tower was conducted in this study. A closed cooling tower is a device similar to a general cooling tower, but with cooling tower replaced by a heat exchanger. The test section for this experiment has the process that the cooling water flows from the top of the heat exchanger to the bottom side in the inner part of the tube, and spray water flows in the gravitational direction in the outer side. Air comes in direct contact with the spray water at the outer side of the tube while passing from the lower the upper part having a counterflow to the spray water. The heat transfer pipe used in this experiment is a bare-type tube having an outer diameter of 15.88mm. The heat exchanger is consisted of seven rows and fifteen columns. In this experiment, thermal performance of the cooling tower is derived from overall heat transfer coefficients between the process fluid and sprayed water and volumetric overall mass transfer coefficient between sprayed water and air.
Keywords