Abstract
This paper proposes the influences of harmonic current on electrical characteristics of an induction motor. Recently, a power system gets more worse as nonlinear load makes harmonics to affect energy lose of system and shorten lift of machines. In this paper, the electrical effect and THD(Total Harmonic Distortion) of harmonic current to an induction motor which is of great use in the industrial fields are measured and analyzed. A power conversion equipment(inverter) is installed to produce harmonics and variable reactors are installed to reduce the harmonics having an effect on the input terminal. Then the effects of the reactors are measured and analyzed. Also average voltage, current, power and 110 by harmonics are analyzed. The results show that Inn is increased by increasing load of the induction motor and installing reactors. And the harmonics affecting the input terminal are decreased by increasing reactor 3[mH] to 6[mH], however, average power of the induction motor is decreased. Therefore, it is very important that reactors should be carefully installed considering the merits and demerits resulting from the installation of reactors.