Analysis of Ventilation Performance Using a Model Chamber

  • Published : 2005.11.01

Abstract

In this study, three different types of mechanical ventilation systems are compared based on their ventilation characteristics: tracer gas concentration decay characteristics, and ventilation effectiveness by calculating actual ventilation air flow rate. The experiments are performed by using a step-down method for measuring tracer gas. $CO_{2}$ gas, concentration in the model chamber. Application of a mixing factor, k, was used and measured values ranged from 0.68 to 0.77. The Type 2 ventilation system was found to have the highest ventilation effectiveness rather than the Types 1 and 3.

Keywords

References

  1. H. T. Han, S. Y. Seo, and Y. I. Kim, 'Ventilation effectiveness measurements utilizing a tracer gas in an under floor air-conditioning space', Journal of Air-Conditioning and Refrigeration Vol. 10, No. 5, pp. 610-618, 1998
  2. H. T. Han, 'Measurement of indoor ventilation effectiveness with location of supply and variation of air flow rate', Proceeding of Summer Symposium of Air-Conditioning and Refrigeration, pp. 372-378, 1999
  3. S. D. Kim, 'The Spatial Characteristics of Ventilation Efficiency', Journal of Korean Society for Atmospheric Environment Vol. 9, No. 3, pp. 236-241, 1993
  4. Bjarne W. Olesen, 'Evaluation of a Vertical Displacement Ventilation System'. Building and Environment, Vol. 29, No. 3, pp. 303-310, 1994 https://doi.org/10.1016/0360-1323(94)90027-2
  5. T. W. Kang, ''A Study on Ventilation Performance and Cooling Load Evaluation of a Room Air Conditioner', Pusan National University Ph. D. Thesis, 2002
  6. J. J. Lee, 'Study on Indoor Air Quality Using Model Chamber'. The University of Seoul Ph. D. Thesis, 1995
  7. R. Hasebe, 'Ventilation Performance and Thermal Comfort for Displacement Ventilation System in Office Space'. Indoor Air 96 I, pp. 823-828, 1996
  8. C. S. Lee, 'Research on Evaluation Method of Indoor Environmental Comfort'. Korea Advanced Institute of Science and Technology, pp. 137-163, 1994
  9. ASRAE, 'Fundamentals of ASHRAE Handbook', American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc., Atlanta, GA 30329, 2005
  10. P. J. Drivas, P. G. Simmonds, and F. H. Shair, 'Experimental Characterization of Ventilation Systems in Building' Environmental Science Technology, Vol. 6, No 7. 1972
  11. American Society for Testing and Materials, 'E741-83, Standard Test Method for Determining Air Leakage Rate by Tracer Dilution', Philadelphia, PA. 1983