A Study on the Factors Affecting the Performance of Paper Heat Exchanger for Exhaust Heat Recovery

배기열 회수용 종이 열교환기의 성능에 영향을 미치는 인자에 관한 연구

  • Chung Min-Ho (Unutilized Energy Research Center, Korea Institute of Energy Research) ;
  • Yoo Seong-Yeon (Department of Mechanical Design Engineering, Chungnam National University)
  • 정민호 (한국에너지기술연구원 미활용에너지연구센터) ;
  • 유성연 (충남대학교 기계설계공학과)
  • Published : 2005.10.01

Abstract

In order to control indoor air quality and save energy, it is needed to install a suitable ventilation system equipped with heat exchanger for heat recovery The purpose of this research is to find the factors affecting the performance of paper heat exchanger for exhaust heat recovery, which can be applied directly to the conventional ventilation unit, air-purifier, and air-conditioning system. In this study, thermal performance and pressure loss of the paper heat exchanger are measured and compared at various operating conditions. The effectiveness of sensible, latent and total heat at the face velocity of 0.75 m/s are $77\%,\;47\%\;and\;57\%$ in the cooling condition and $77\%,\;59\%,\;and\;\%$ in the heating condition, respectively. The effectiveness for sensible heat is only affected by velocity. On the other hand, the effectiveness for latent heat is affected. by temperature and relative humidity.

Keywords

References

  1. Yoo, S. Y., Chung, M. H., Kim, K. H. and Lee, J. M., 2005, An experimental study on the performance of plastic plate heat exchanger, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 17, No. 2, pp. 117-124
  2. Yoo, S. Y., Chung, M. H., Kim, K. H. and Lee, Y. M., 2002, A study on the performance of plastic plate heat exchanger, Proceedings of SAREK 2002 Summer Annual Conference, pp. 178-183
  3. Webb, R. L., 1994, Principles of Enhanced Heat Transfer, Wiley Interscience
  4. Kilicashan, I. and Sarac, H. I., 1998, Enhancement of heat transfer in compact heat exchanger by different type of rib with holographic interferometry, Experimental Thermal and Fluid Science, Vol. 17, pp.339-346 https://doi.org/10.1016/S0894-1777(98)00006-5
  5. Yoo, S. Y., Chung, M. H., Kim, K. Y., Lee, C. W. and Lee, K.S., 2003, A study on the factors affecting the performance of total heat exchanger for exhaust heat recovery, Proceedings of SAREK 2003 Summer Annual Conference, pp.280-285
  6. Bai, C. H., Chung, M., Kim, S. Y., Lim, Y. H., Nasriddinovna, D. G., Yun, B., Kim, Y S. and Park, C. J., 2002, The comparison study of energy performance for heat recovery ventilator, Proceedings of SAREK 2002 Summer Annual Conference, pp. 518-523
  7. Lee, C. W., Lee, K. S., Koh, D. Y. and Yeom, H. K., 2001, Design and test of heat recovery ventilator with total heat exchanger, Proceedings of SAREK 2001 Summer Annual Conference, pp. 512-516
  8. Korean Industrial Standard M 7020, 1995, Testing method for air permeability of paper and paperboard
  9. Korean Industrial Standard M 7019, 1995, Testing method for water vapor permeability of paper and paperboard
  10. ASHRAE Standard-84, 1991, Method of testing air-to-air heat exchangers
  11. Japanese Industrial Standard-B 8628, 2000, Air to air heat exchanger
  12. Kline, S. J. and McClintock, F. A., 1953, Describing uncertainties in single-sample experiments, Mechanical Engineering, pp. 3-8