DOI QR코드

DOI QR Code

Analysis of fault Current Limiting Characteristics due to Ratio of Inductances between Coil 1 and coil 2 in a Flux-lock Type SFCL

자속구속형 고온초전도 전류제한기의 인덕턴스 변화에 따른 전류제한 특성 분석

  • 박충렬 (전북대학교 전기공학과) ;
  • 임성훈 (전북대학교 공업기술연구센터) ;
  • 박형민 (조선대학교 전기공학과) ;
  • 최효상 (조선대학교 전기공학과) ;
  • 한병성 (전북대학교 전기공학과)
  • Published : 2005.09.01

Abstract

A flux-lock type SFCL consists of two coils, which are wound in parallel each other through an iron core, and a HTSC thin film connected in series with coil 2. If the current of the HTSC thin film exceeds its critical current by the fault accident, the resistance generated of the HTSC thin film, and thereby the fault current can be limited by the impedance of the flux-lock type SFCL. The amplitude of fault current can be set by the impedance of the flux-lock type SFCL. In this paper, we investigated the variance of the limiting current due to the ratio of inductances between coil 1 and coil 2 in the flux-lock type SFCL through the computer simulations and short circuit tests. In addition, both the simulation results and experimental ones were compared each other. From the comparison of both the results, the simulation results agreed well with the experimental ones.

Keywords

References

  1. 김준환, 이강완, '전력계통, 고장전류 증대와 대응방안', 전기저널, 1권, 2호, p. 19, 1998
  2. L. salasoo, A. F. Imece, R. W. Delmerico, and R. D. Wyatt, 'Comparison of super-conducting fault limiter concepts in elecrtic utility applications', IEEE Trans, on Appl. Supercond., Vol. 5, No. 2, p. 1079, 1995
  3. 임성훈, 최명호, 이현수, 한병성, '차폐유도형 고온초전도 전류제한기의 설계 및 특성 시뮬레이션,' 전기학회논문지, 48C권, 3호, p. 173, 1999
  4. 최효상, 현옥배, 김혜림, 황시들, '15kVA 금박막형 초전도 전류제한기의 한류특성', 전기전자재료학회논문지, 13권, 12호, p.1058, 2000
  5. 조동원, 박경국, 김동원, 정길도, 한병성, '고온초전도 전류제한기용 후막의 특성 연구', 전기전자재료학회논문지, 11권, 12호, p. 1139, 1998
  6. 김태중, 강형구, 고태국, '유도형 고온초전도 한류기용 prototype 직류 리엑터의 설계 및 제작', 전기전자재료학회논문지, 16권, 12S호, p.1292, 2003
  7. B. Gromoll, G. Ries, W. Schmidit, H.-P. Kraemer, B. Seebacher, B. Utz, R. Nies, H.-W. Newmuller, E. Baltzer, and S. Fischer, 'Resistive fault current limiters with YBCO films-100 kVA functional model', IEEE Trans, on Appl. Supercond., Vol. 9, No. 2, p. 656, 1999 https://doi.org/10.1109/77.783381
  8. M. Yamaguchi, S. Fukui, T. Satoh, Y. Kaburaki, T. Horikawa, and T. Honjo, 'Performance of DC reactor type fault current limiter using high temperature superconducting coil', IEEE Trans, on Appl. Supercond., Vol. 9, No. 2, p. 940, 1999
  9. 박충렬, 임성훈, 박형민, 최효상, 한병성, '자속구속형 전류제한기의 초기 사고전류 제한시점 변화', 전기전자재료학회논문지, 18권, 3호, p. 269, 2005

Cited by

  1. Analysis of Fault Current Limiting Characteristics According to Variation of Inductances in Separated Three-phase Flux-lock Type SFCL vol.22, pp.6, 2009, https://doi.org/10.4313/JKEM.2009.22.6.522