A Study on the Cooling Characteristics of TMA by an Additive

첨가제에 의한 TMA의 냉각특성에 대한 연구

  • Chung Nak-Kyu (Department Mechanical Design Engineering, Chosun University) ;
  • Kim Jin-Heung (Department Mechanical Engineering, Chosun University) ;
  • Kim Chang-Oh (Department Mechanical Design Engineering, Chosun University) ;
  • Kang Seung-Hyun (Department Mechanical Design Engineering, Graduate School, Chosun University)
  • 정낙규 (조선대학교 기계공학과) ;
  • 김진흥 (조선대학교 기계설계공학과) ;
  • 김창오 (조선대학교 기계공학과) ;
  • 강승현 (조선대학교 대학원 기계설계공학과)
  • Published : 2005.06.01

Abstract

This study is performed to investigate the cooling characteristics of TMA $25\;wt\%$ clathrate compound with an additive; the phase change temperature, the degree of supercooling, specific heat and the rate of volume change. The used additive is ethanol and the heat source temperature is $-7^{\circ}C$. Experimental results are as follows: 1) The phase change temperature is increased by $0.32\~0.96^{\circ}C$ during the cooling process of TMA $25\;wt\%$ clathrate compound with ethanol. 2) The degree of supercooling is repressed by $0.9^{\circ}C$ in case of TMA $25\;wt\%$ clathrate compound with $0.5\;wt\%$ ethanol. 3) The specific heat is increased by $0.19\;kJ/kg^{\circ}C$ in case of TMA $25\;wt\%$ clathrate compound with $0.l\;wt\%$ ethanol. 4) The rate of volume change is decreased by $1.15\~l.5\%$ in case of TMA $25\;wt\%$ clathrate compound with ethanol.

본 연구에서는 TMA $25\;wt\%$-물계 포접화합물에 첨가제를 첨가하며 상변화온도, 과냉도, 비열 그리고 체적변화율의 냉각특성에 대한 실험적 연구를 수행하였다 사용된 첨가제는 에탄올 이며, 냉열원온도는 $-7^{\circ}C$이다. 실험결과들은 다음과 같다. 1) 상변화온도는 $25\;wt\%$-물계 포접화합물에 에탄올을 첨가하여 냉각과정동안 $0.32\~0.96^{\circ}C$가 상승되었다. 2) 과냉도는 TMA $25\;wt\%$-물계 포접화합물에 에탄올 $0.5\;wt\%$를 첨가한 경우에 $0.9^{\circ}C$가 억제되었다. 3) 비열은 TMA $25\;wt\%$-물계 포접화합물에 에탄올 $0.1\;wt\%$를 첨가한 경우에 $0.19\;kJ/kg^{\circ}C$가 증가하였다. 4) 체적변화율은 TMA $25\;wt\%$-물계 포접화합물에 에탄올을 첨가한 경우에 $1.15\~l.5\%$가 감소하였다.

Keywords

References

  1. Kim., J.D. 'To Society Serious Energy Efficiency Conversion', Journal of Energy Management, Korea Energy Management Corporation, 1998, 2, 36-39
  2. Im, D.H. 'Ice Thermal Storage System', Korean Assoiciation of Air Conditioning Refrigerating and Sanitary Engineers, 1998, 34-41
  3. Yang, Y.S. 'Local Energy Practical Use Base Technical Development', Korea Institute of Energy Research, KE-93002G, 1993
  4. Yang, Y.S.; Bak, N.C.; Lee, D.W.; Park, Y.H. 'Energy System Supporting Research of Green House', Korea Institute of Energy Research, KIER-971232, 1997
  5. Tanino, M.; Kozawa, Y Ice-water two-phase flow behavior in ice heat-storage systems. Int. J. Ref., 2001, 24(7), 639.51
  6. Sloan ED. Clathrate hydrates of natural gases. New York: Marcel Dekker; 1997
  7. OGOSHI Hidemasa, et al. Air-Condition-ing System Using Clathrate Hydrate Slurry. JFE TECHNICAL REPORT No.3 (July 2004)
  8. Kim, J.H.; Chung, N.K.; Han, Y.O. 'A Study on Cooling Characteristics of Clathrate Compound for Cold Storage Applications', Korean Journal of Air-Conditioning and Refrigeration Engineering, 2000, 12(8), 725-734