A study on SFCL systems for power system application

실계통적용을 위한 초전도한류시스템에 대한 연구

  • Published : 2005.03.01

Abstract

The recovery time of developing SFCL(Superconducting Fault Current Limiter) has an uncertainty. In general, the recovery time is estimated at 1 sec and more, even though the Process of SFCL technology is considered. However, auto reclosing time of circuit breaker is 0.3 sec in Korean power system. It is impossible to apply only one SFCL to power system because the recovery time is over the reclosing time of protection system. This study proposes two new SFCL systems for power system application. The proposed systems consider auto reclosing action for the protection in practical power system and consist of tow parallel SFCLS.