Analysis on the Operation Characteristics of Induction Motor Operated by Symmetric Unbalanced Voltage

대칭 불평형 전압 운전시 유도전동기의 동작 특성 해석

  • Received : 2004.02.25
  • Accepted : 2004.05.14
  • Published : 2004.09.01

Abstract

Most of the loads in industrial power distribution systems are balanced and connected to three power systems. However, in the user power distribution systems, most of the loads are single & three phase and unbalanced, generating voltage unbalance. This paper presents a scheme on operation states of a three-phase induction motor under unbalanced voltages. The three-phase voltages applied to the stator winding of the studied induction motor are controlled by respectively adjusting the magnitude and phase angle of each phase. The voltage unbalanced factor(VUF) of the three-phase source voltages can then be varied to examine the different values of VUF on machine's operation characteristics.

Keywords