Directional Water Spray Characteristics of Sprinkler Heads

스프링클러 헤드의 방향성 살수 특성 비교 연구

  • Published : 2004.12.01

Abstract

The water spray characteristics of the sprinkler heads is a very important factor affecting the fire suppression performance, and it is largely dependent on the shape of the head nozzle. This study investigated shape factors and spray distribution performances for the sprinkler heads of four domestic companies with big market shares. The experimental results revealed that all flow constants exceeded the required regulation limits, however showed big differences between head types although they have the same design limit. They were however relatively consistent regardless of the pressure increases. The spray distribution of some head samples showed severe directional eccentricity, which suggests more study for the improvement.

스프링클러 헤드의 살수 특성은 화재의 초기 진화 성능을 결정짓는 매우 중요한 요소이며, 이는 헤드노즐의 형상에 크게 좌우된다. 본 연구에서는 국내 시장점유율이 가장 높은 4개 제조사의 헤드 제품군에 대하여 방수계수 값과 방향성 살수 분포 특성을 규명하였다. 방수계수는 모두 기준 값을 상회하였지만, 헤드 종류별로 동일한 설계 값을 가짐에도 불구하고 큰 차이를 보이는 것으로 나타나 제품 간 품질차이가 큰 것으로 나타났다. 다만, 방수계수는 압력변화에 관계없이 비교적 일정하게 나타났다. 방향별 살수 분포 특성은 일부 헤드 샘플의 경우 매우 심각한 편향 분포를 나타냄으로써 성능개선 연구가 시급한 것으로 판단되었다

Keywords

References

  1. 진중신, '주택에서의 스프링클러설비의 경제성에 대한 연구(III)', 소방 2000년, No. 9, pp90-97(1990)
  2. 이춘하 외, '주거용 스프링클러 설비의 도입에 관한 연구', 한국화재소방학회 추계학술대회 논문집, pp252-258(2001)
  3. 행정자치부, '스프링클러헤드의 검정기술기준', KOFEIS 0501 (1999)
  4. 백창선, '스프링클러헤드 살수분포 시험장치 및 유수검지시험장치', 소방검정 25호(1995)
  5. 권오승, '스프링클러헤드 성능 시험연구', 방재기술, 방재시험소(1987)
  6. '스프링클러 소화설비의 소화시간', Fire Safety Science Proceeding of the First International Symposium, 방재기술(1985)
  7. E. Hinkey, 'Hydraulics for Fire Production', Royal Soc, No. 17(1980)