Abstract
This paper presents how to find proper operating points of FACTS devices to enhance the steady-state security level considering line contigency analysis. Three generic types of FACTS devices such as series controllers, shunt controllers, and series-shunt controllers are introduced and applied to moximize a security margin and to minimize security indices. Security indices related to line flows and bus voltages are utilized and minimized iteratively in this paper. Contingency analysis is performed to detect the most severe single line fault. In various load conditions, FACTS devices are tested to establish appropriate preventive or corrective action without generation re-dispatching or load shedding. The FACTS operation scheme is verified on the IEEE 57-bus system in a line-faulted contingency.
본 논문에서는 상정사고 해석을 통해 결정된 가장 심각한 단일 선로고장에 대하여 부하차단이나 재급전을 하지 않고, 유연송전기기의 운전만으로 안전도를 향상시켜 이를 극복할 수 있는 방법을 제시하였다. 즉, 직렬, 병렬, 직병렬보상기기 등 유연송전기기의 각 종류별로 정적 안전도 여유를 최대화하고 안전도 지수를 최소화하는 방법을 개발하였고, 이를 통하여 각 유연송전기기의 최적 운전점을 결정하는 방법을 개발하였다. 여기서, 정적 안전도 지수는 선로 조류 및 모선 전압에 관한 안전도를 정량화하여 식으로 나타낸 것이다. 안전도 지수가 작아지면 안전도 여유는 커지는데, 본 논문에서는 안전도 지수를 반복계산법으로 최소화하였다. 본 논문에서는 제안한 방법은 IEEE 57모션개통에 적용하여 제안된 방법의 정당성을 수치적으로 입증하였다.