Study on Fresh Air Load Reduction System by Using Geothermal Energy - Reducing Effect of a Fresh Air Load by Combining with Air-heated Solar Collector -

지열을 이용한 공조외기부하저감 시스템에 관한 연구 - 공기식 집열기와의 병용에 의한 공조외기부하저감 효과 -

  • 손원득 (일본 삼중대학교 공동벤처연구기관) ;
  • 이성 (동의대학교 빌딩시스템공학과)
  • Published : 2004.12.01

Abstract

This paper presents thermal behaviors and performances of a fresh air load reduction system by using earth tube system combined with air-heated solar collector. The earth tube system reduces a fresh air load by heat exchange with soil throughout the year. In the previous experimental research, it was clarified that the earth tube system was very useful as a fresh air load reduction system. However, since outlet temperature of the fresh air which was heated by earth tube system was below 15$^{\circ}C$ in winter, it is not suitable to introduce the fresh air into the place of residence directly. Therefore, a simulation model using the simple heat diffusion equation was used to examine a rising effect of outlet air temperature in winter by combining with air-heated solar collector. An improvement of annual performance by control of operation is also quantitatively examined. In conclusion, it is confirmed that its performance is improved by control of operation throughout the year and outlet air temperature rose by combining with air-heated solar collector.

Keywords

References

  1. Lee, S. B., Kim, G. H. and Lee, M. K, 2002, A study on energy saving potential in multi-family residential complex using mass cooling effects, Journal of AIK, Vol. 18, No.1, pp.217-224
  2. Park, H. S., 1995, A study on heat and mass transfer of the natural cooling system using the underground energy, Journal of AIK, Vol. 11, No. 10, pp. 187-197
  3. Zhang, Q. and Ishihara, 0., 1995, Discussion on the exit temperature and cooling energy of cooling tubes for design, Journal of AIJ, No. 477, pp. 11-18
  4. Kimura, K, Maeda, K and Onojima, H., 1983, Study on the passive cooling effects of cool tube, Summaries of technical paper of annual meeting, AIJ, pp.675-678
  5. Chun, W. G., Lim, S. H., Jean, M. S. and Yoon, J. H., 1992, A study on the air system for space heating, Journal of the Korean Solar Energy Society, Vol. 12, No.1, pp.34-39
  6. Kim, B. C., Shin, H.J., Choi, K H. and Kum, J. S., 2000, Study on the collector efficiency of an air heater in a solar air conditioning system, Journal of the Korean Solar Energy Society, Vol. 20, No.4, pp. 1-8
  7. Park, J.U., Lee, E.J. and Chung, M., 2003, Study on development of subroutine based on TRNSYS for unglazed transpired air collector system, Journal of the Korean Solar Energy Society, Vol. 23, No.2, pp.81-90
  8. Son, W. T., Nagai, H. and Okumiya, M., 2001, Part 10: The examination on model taking account of hygroscopic concrete, Summaries of technical papers of annual meeting, AIJ D-2, pp. 503-504
  9. Hottel, H. C. and Whillier, A., 1958, Trans. Conf. Use of Solar Energy, University Arizona, Vol. 2, p. 74