Abstract
To predict the temperature distribution around a underground rock storage cavern, two- and three- dimensional numerical analysis using FLAC was conducted. The effects of groundwater and latent heat on thermal properties were considered in numerical calculation. The temperature estimated by FLAC are compared with the temperature measured for 5-year operation at Gonjiam storage cavern. Estimated and measured temperatures showed great discrepancy when thermal properties from laboratory tests were used and showed good agreement when the effects from 20% of volumetric water fraction and latent heat were considered. However, the discrepancy still increased with operation time due to the heat flow from ground surface. Three-dimensional numerical models were established to closely approximate the boundary condition of the test site, and numerical results better agreement when groundwater and latent heat effects were considered.
지하암반 냉동저장고 주변의 온도분포를 예측하기 위하여, FLAC을 이용한 2차원 및 3차원 수치해석을 수행하였다. 수치해석 수행 시 암반 열물성에 대한 지하수 및 동결잠열의 영향을 고려하였으며, 2차원 및 3차원 수치해석 결과와 5년간의 지하암반 온도계측 자료를 비교하였다. 2차원 수치해석 결과 실험실 물성을 이용한 경우는 계측 결과와 큰 오차를 나타내었으며, 지하수 부피비 20% 및 동결잠열을 고려한 수치해석 결과가 계측 결과와 가장 작은 오차를 나타내었다. 하지만, 냉동기 가동시간이 증가하면서 지표면으로의 열 유동의 영향으로 커지는 오차는 커지는 경향을 나타내었다. 지표면의 영향을 고려하는 3차원 수치모델을 정립하여 수치해석을 수행한 결과, 지하수 및 동결잠열의 영향을 고려한 수치모델이 계측 결과가 잘 일치하는 경향을 나타내었다.