Abstract
With the proliferation of nonlinear loads, high neutral harmonic currents in three-phase four-wire distribution system have been observed. It has been known that the ground impedance has an effect on the neutral currents of a system which operates with harmonics present. On-site measurements of harmonic currents and voltages according to the fall-of-potential method under case study system were made and the ground impedance modeling using the pattern search method for the harmonic analysis was developed The ground impedance model obtained by the proposed method was compared with the frequency characteristics by field tests and has shown appropriate results, and would be applicable to evaluate the harmonic and transient response characteristics of the ground system.
3상 4선식 배전계통을 채용하는 우리나라는 비선형 부하의 증가로 중성선에는 많은 중성선 고조파 전류가 관측되고 있다. 또한 접지 임피던스는 고조파가 있는 중성선 전류에 영향 끼친다고 알려져 있다. 전위 강하법에 따라 현장에서 실측한 고조파 전류와 전압을 측정하고, Pattern Search 기법으로 고조파 해석용 접지 임피던스를 모델링 하였다. 여기서 구한 임피던스 모델은 현장 시험에 의한 임피던스 모델과 비교하여 유사한 결과를 얻었고, 접지 시스템의 고조파 및 과도 응답 특성을 평가하는데 활용될 것으로 사료된다.