A Study on Smoke Movement by Using Large Eddy Simulation I. Smoke Control Systems and Extraction Flowrate

대와류모사를 이용한 연기이동의 연구 I. 제연방식과 배기풍량

  • Published : 2003.06.01

Abstract

To evaluate the smoke control systems, the large eddy simulation turbulence model based Fire Dynamics Simulate was applied to a 2m $\times$ 2m $\times$ 2.4m room with an opening. The smoke removal rate was investigated for three different smoke control systems: ventilation, extraction and pressurization. When the opening was closed, the smoke removal rates of the smoke control systems were almost the same as expected. The pressurization system showed a lower smoke removal rate compared with the other two smoke control systems for the room with the opening, and hence the pressurization system might not be efficient for a place with large openings. It was shown that the lower extraction flowrate is, the longer time the ventilation system requires to remove smoke. From these results, the ventilation system is recommended for subway stations where several large openings exist.

Keywords

References

  1. 추병길, 박찬국, 방배연설비 실무, 동화기술, pp.212, 1995
  2. 이성룡, 정진용, 김충익, 유홍선, '터널화재시 환기방식에 따른 연기거동에 관한 실험적 연구,' 설비공학논문집, 제14권, 제9호, pp. 691-698, 2002
  3. K. B. McGrattan, H. R. Baum, R G. Rehm, A. Hamins, G. P, Forney, J. E. Floyd and S. Hostikka, Fire Dynamics Simulator Technical Reference Guide v.3, NIST, Gaithersburg, Maryland, U.S.A
  4. 박외철, 고경찬, '닥트 두께가 대향류 화염구조에 미치는 영향의조사,' 산업안전학회지, 제17권, 제4호, pp. 61-65, 2002
  5. 박외철, 정락기, '공동주택 보일러 연소배기가스의 실내유입에 관한 연구,' 설비공학논문집 투고, 2003
  6. J. Smagorinsky, 'General Circulation Experiments with the Primitive Equations I. The Basic Experiment,' Monthly Weather Review, Vol. 91, pp. 99-164, 1963 https://doi.org/10.1175/1520-0493(1963)091<0099:GCEWTP>2.3.CO;2