A Study on the Application of VAV/BPFS(Variable-Air-Volume/Bypass Filtration System) for Indoor Air Environment

VAV/BPFS(Variable-Air-Volume/Bypass Filtration System) 의 실내환경 적응에 관한 연구

  • Published : 2003.12.01

Abstract

Under controlled conditions in an environmental chamber, 24 experiments were performed to compare the ability of a Variable-Air-Volume/Bypass Filtration System(VAV/BPFS) to remove indoor pollutants and to conserve energy with the ability of conventional Variable Air Volume(VAV) system. The specific conclusions of this paper were; first, the VAV/BPFS was more efficient than the VAV system in removing particulate matter, TVOC, and target VOCs. The total effective removal rate of PM for the VAV/BPFS was two times as high as that of the VAV system. The total effective removal rate of TVOC for the VAV/BPFS was 20 percent higher than that of the VAV system. Also each target VOC concentration was reduced by using the VAV/BPFS. Second, clean air delivery rate was increased by using VAV/BPFS due to additional filtration rate. Otherwise, the VAV/BPFS decreased outdoor supply air rate above 25 percent relative to the rate of VAV system. Third, total energy consumption by the VAV/BPFS was lower than that of the VAV system during the period with indoor thermal load, occupied time. The energy saving of the VAV/BPFS ranged from 11 to 16 percent. The VAV/BPFS improves indoor air quality more efficiently than the VAV system, and it reduced energy consumption. Retrofitting the VAV system with the VAV/BPFS was easy The use of VAV/BPFS is, therefore, recommended far buildings with VAV system as well as for buildings at designing stage.

Keywords

References

  1. Lee, C. S., W. M. Li and C. H. Ao, 2002, Investigation of indoor air quality at residential homes in Hong Kong-case study, Atmospheric Environment, 36, 225-237. https://doi.org/10.1016/S1352-2310(01)00435-6
  2. Junker, M., T. Koller. and C. Monn, 2000, An assessment of indoor air contaminants in buildings with recreational activity, The Science of the Total Environment, 246, 139-152. https://doi.org/10.1016/S0048-9697(99)00452-0
  3. ones, A. P., 1999, Indoor air quality and health, Atmospheric Environment, 33, 4535-4564. https://doi.org/10.1016/S1352-2310(99)00272-1
  4. Wargocki, P., Z. Bako-Biro, G. Clausen and P. O. Fanger, 2002, Air quality in a simulated office environment as a result of reducing pollution sources and increasing ventilation, Energy and Buildings, 34, 775-783. https://doi.org/10.1016/S0378-7788(02)00096-8
  5. Redlich, C. A., J. Sparer and M.. Cullen, 1997, Sick-building syndrome, The Lancet, 349, 1013-1016. https://doi.org/10.1016/S0140-6736(96)07220-0
  6. Grot, R.A., A.T. Hodgson, J.M. Daisey and A. Persily, 1991, Indoor air quality evaluation of a new office building, ASHRAE Journal, 33, 16-25.
  7. Molhave, L. and M. A. Thorsen, 1991, A model for investigations of ventilation systems as sources for volatile organic compounds in indoor climate, Atmospheric Environment, 25a, 241-249.
  8. ASHRAE Standard 62-1989, 1989, Ventilation for acceptable indoor air quality, American Society of Heating, Refrigerating and Air Conditioning Engineers, Atlanta, GA, ASHRAE Publications.
  9. Choi, S. W., 1996, Indoor air quality: An overview of emission sources and control strategies, Journal of Nokdong Environmental Research Institute, 1, 113-134.
  10. ASHRAE, 1985, System Handbook, American Society of Heating, Refrigerating and Air Conditioning Engineers, Atlanta, GA, ASHRAE Publications.
  11. Sauer, Jr. H.J. and R.H. Howel, 1992, Estimating the indoor air quality and energy performance of VAV system, ASHRAE Journal, 7, 43-50.
  12. Mcquiston, F.C. and J.D. Parker, 1988, Heating, ventilation, and air conditioning analysis and design, third edition, John Wiley & Sons, NY.
  13. Rickelton, D. and H.P. Becker, 1972, Variable Air Volume, ASHRAE Journal, 9, 31-55.
  14. hoi, S.W., D.J. Moschandreas and M. Meckler, 1995, Testing of VAV/BPFS for reduced energy consumption and improved IAQ, IAQ, 95, 31-35.
  15. Moschandreas, D.J., S.W. Choi and M. Meckler, 1994, Variable-air-volume/bypass filtration system(VAV/BPFS) performance with respect to indoor air quality, Healthy Buildings 94, Proceedings of the 3rd International Conference, 2, 455-460.
  16. 최성우, 1997, 실내공기질 모델을 이용한 환기시스템의 공기정화효율성 평가, 한국환경위생학회지, 23(4), 57-66.