Effect of Phosphate-based Inhibitors on Pipe Corrosion of Drinking Water Supply

상수도 배급수관망의 부식방지를 위한 인산염계 방청제 적용에 관한 연구

  • 이윤진 (건국대학교 환경공학과) ;
  • 남상호 (건국대학교 환경공학과)
  • Published : 2003.09.01

Abstract

The injection concentration of corrosion inhibitor increases under the pH 7, temperature of 2$0^{\circ}C$, and alkalinity of 35 mg/l (as CaCO$_3$), the corrosion rate gradually decreased. When the corrosion inhibitor of 10 mg/l is injected, the corrosion rate for carbon steel pipe, galvanized steel pipe, and copper pipe reduces for 37, 66 and 61 % respectively that it is more efficient on galvanized steel pipe and copper pipe. As a result of examination of corrosion rate at pH 6, 7, and 8 when injecting 10 mg/l of corrosion inhibitor under the conditions of 2$0^{\circ}C$ in water temperature and 35 mg/l (as CaCO$_3$) in alkalinity, the efficiency of the corrosion inhibitor increases as the pH increases. For carbon steel pipe, it does not show much a difference with the change of the pH condition, but galvanized steel pipe and copper pipe clearly show the corrosion rate depending on the change of the pH condition. The efficiency of corrosion inhibitor is low as the concentration of residual chlorine is high, but it does not show a great influence at 0.4 mg/l or less. For each pipe type, in the case of carbon steel pipe, the range of increase of corrosion speed following the residual chloride is higher than the other pipe types. In the meantime, the effect following the residual chlorine in copper pipe is low.

Keywords

References

  1. Costello, J. J. : Corrosion control within water distribution systems. AWWA Annual Conference Proc., 86-95, 1981
  2. 남상호 : 상수도 배.급수관에서의 수질 변화와 그 대책. 제 25회 수도심포지엄논문집,7-64、1993
  3. 이현동 : 수도관로의 관리상태와 방안,수도,69,한국 수도협회, 1994
  4. 곽필재,이현동,남상호,정원식 : 국내수계별 수돗물의 부식성 및 금속용출특성평가에 관한 연구. 대한환경공학회지,23(7),1195-1203, 2001
  5. Mullen, E. D. and Ritter, J. A. : Portable water corrosion control. Jour. AWWA, 473-486, 1974
  6. 김선일 : pH와 알칼리도와 염소이온이 동관의 부식에 미치는 영향. 건국대학교 석사학위 논문,1999
  7. APHA, AWWA and WEF : Standard methods for the examination of water and wastewater, 19th edition, American Public Health Association, Washinton, 1995
  8. Wolfel, P. : Case study-central phosphate dosage to reduce red water and zinkgeriesel in house installations-two field experiments at walbingen and stuttgart. Landeswasserversorgung, Stuttgart, 1983
  9. AWWA : Water quality and treatment, 5th Ed, McGRAW-Hill, New York. 14. 22-32, 1999
  10. 환경부 : 고도정수기술 : 수돗물의 2차오염 방지기술,1999
  11. Lane, R. W., Larson, T. E. and Schilsky, S. W. : The effect of pH on the silicate treatment of hot water in galvanized piping. Jour. AWWA, 69(8), 457-460, 1977 https://doi.org/10.1002/j.1551-8833.1977.tb06789.x
  12. Larson, T. E. and Buswell, A. M. : Calcium carbonate saturation index and alkalinity determination. Jour. AWWA, 1667-1676, 1942
  13. LeChevallier, M. W., Chery, C. D., Lee, R. G. and Gibbon, D. L. : Examining the relationship between iron corrosion and the disinfection of biofilm bacteria. Jour. AWWA, 85(2), 111-123, 1993 https://doi.org/10.1002/j.1551-8833.1993.tb06031.x
  14. Lin, C. F. and Benjamin,M. M.: Dissolution kinetics of minerals in the presence of sorbing and complexing ligands. Environ. Sci., 24(1), 126-134, 1976
  15. 이의호,이학렬,황운석,김광근 : 부식과 방식의 원리 . 동화기술,1999