Abstract

Nowadays, one of the serious problems in KEPCO(Korea Electric Power Co-Operation) system is the more higher fault current than the SCC(Short Circuit Capacity) of circuit breaker. There are many alternatives to reduce the increased fault current such as isolations of bus ties, enhancement of SCC of circuit breaker, applications of HVDC-BTB(High Voltage Direct Current-Back to Back) and FCL(fault current limiter). But, these alternatives have some drawbacks in viewpoints of system stability and cost. As the superconductivity technology has been developed, the HTS-FCL(High Temperature Superconductor -Fault Current Limiter) can be one of the attractive alternatives to solve the fault current problem. Under this background, this paper presents the EMTDC(Electro-Magnetic Transient Direct Current) model for resistance type HTS-FCL considering the nonlinear characteristic of final resistance value when quenching phenomena occur.

Keywords

References

  1. 계통특성 개선설비 설치 타당성 검토 보고서 한국전력공사 전원계획처
  2. 초고압 대용량 직류송전 기술개발 한국전기연구원
  3. HTS-FCL 특성비교 검토 한국전기연구원
  4. IEEE Transactioms on applied superconductivity Technical and economical benefits of superconducting fault current limiters in power systems M.Noe;B.R.Oswald
  5. IEEE Trans. Appl. Supercond v.9 Applications of HTS fault current limiters in the danish utility network J.N.Nielsen;J.J.Ostergaard
  6. 한밭대 연구보고서 초전도한류기 파라미터 검토 한밭대
  7. IEEE Trans. Appl. Supercond Setting method of specific parameters of a superconducting fault current limiter considering the operation of power system protection H.Kameda
  8. Power System Analysis Charles A.Gross
  9. EMTDC Manual. Custom Model