Abstract
R407C is considered as alternative refrigerant of R22 for air conditioners. Experimental investigation is made to study the condensation heat transfer characteristics of slit fin-tube heat exchanger using alternative refrigerant, R407C. Experiments are carried out at condensation pressure of 2110 kPa and 1943 kPa with the degree of superheat of 1$0^{\circ}C$ and mass flux varying from 150 to 250 kg/$m^2$s for refrigerant side. The inlet air condition is dry bulb temperature of 35$^{\circ}C$, relative humidity of 50% and air velocity varying from 0.8 to 1.6 m/s. Experiments show that pressure drop gets smaller at a higher condensation pressure especially when condensation pressure is raised from 1943 to 2110 kPa. Heat transfer rate gets smaller at a lower condensation pressure in the range of experimental condition.