DOI QR코드

DOI QR Code

The Influences of LiBr Solution Recirculation in Absorber on the Absorption Chiller Performance

흡수기 용액 재순환이 흡수식 냉동기 성능에 미치는 영향

  • Published : 2002.05.01

Abstract

If a part of the poor solution from the absorber outlet is recirculated to the absorber inlet, the solution temperature at the solution spray pump can be reduced, and the solution flow rate in the absorber is increased. We have performed the experiments on the influences of the absorption chiller performance according to the ratio of the recirculation, defined as the ratio of the recirculation flow rate to the total solution flow rate at the absorber outlet. As increasing the ratio of the recirculation, the absorption capacity of the solution can be deteriorated. On the other hand, due to the increasing flow rate, the heat transfer rate can be enhanced. As a result, the performance of the absorber and the cooling capacity of the absorption chiller have nothing to do with the recirculation ratio, and the lifetime of the spray pump will be maintained.

Keywords

References

  1. 김균식, 박지훈, 김춘동, 유병훈, 최고원, 김익생, 2000, '상용 50RT급 흡수식 냉동기 특성 해석,' 공기조화냉동공학회 하계학술발표회 논문집, pp. 972-980
  2. 박문수, 진성민, 박찬우, 정종수, 정봉철, 1999, '흡수식 냉동기용 흡수기의 LiBr 농도 특성 측정,' 공기조화냉동공학회 동계학술발표회 논문집, pp. 439-444
  3. 진성민, 정종수, 정봉철, 최승학, 2000, '중온수 흡수식 냉동기의 냉각수 유량에 따른 특성,' 공기조화냉동공학회 하계학술발표회 논문집, pp. 960-964
  4. 최승학, 정봉철, 남임우, 정종수, 진성민, 2001, '상용 흡수식 냉동기에서 LiBr 수용액 유량변화에 따른 영향,' 대한기계학회 춘계학술대회 논문집 D, pp. 292-297
  5. McNeely, A. L., 1979, 'Thermodynamic Properties of Aqueous Solutions of Litium Bromide,' ASHRAE Transactions 85(1): pp. 413-434
  6. Jongsoo Jurng, Sung min Chin, Chan Woo Park, Seung Hak Choi, and Bong Chul Chung, 2000, 'LiBr Concentration Distribution in a Falling-Film Type Absorber Measured by a Refractometer,' JSME-KSME Thermal Engineering Conference, Vol. 3, pp. 645-649